4. Motion Control Instruction
4-98 DVP-MC operating manual
4.6.17. CTU
API
Controller
144
CTU
Up counter
10MC11T
Explanation of the instruction:
CTU is used to achieve the function of upcounter.
When EN is on, R is off and the count-up input CU turns off -> on, the current value EV of the counter is
increased by 1; as the value of EV is greater than or equal to the preset value PV, the output CTU is on; as
EV reaches the maximum 4294967295, the counter stops counting. As R is on, CTU is reset and the current
value EV of the counter is cleared as 0.
Explanation of input and output parameter of the instruction:
Parameter
name
Explanation
Data
type
Available
device
EN
The execution condition of this instruction.
“CTU” instruction is executed as “EN” turns on; CTU
and EV value keep unchanged as “EN” turns off.
BOOL M,I,Q,constant
CU
Once “CU” turns off -> on, the current value of the
counter is added by 1.
BOOL M,I,Q,constant
R
When “R” turns on, the current value “EV” is cleared to 0
and “CTU” is reset.
BOOL M,I,Q,constant
PV The preset value of the counter. UDINT Constant, D
CTU
When “EN” is on and the current value of “EV” is greater
than or equal to that of “PV”, “CTU” turns on.
BOOL M,Q
EV
The current value of the counter.
When “EN” turns on , “R” is off and the count-up input
CU turns off -> on, the current value is added by 1; as
the value of “EV” is up to the maximum 4294967295,
the counter stops counting.
UDINT D