4. Motion Control Instruction
4-112 DVP-MC operating manual
4.6.25. TONR_ms
API
Controller
152
TONR_ms
Retentive on-delay timer
10MC11T
Explanation of the instruction:
TONR_ms is a retentive on-delay timer with 1ms as the timing unit.
When EN is on and IN is on, the current value ET of the timer starts timing;
When IN is off, the current value ET is maintained. When IN turns on once again, the timing is continued
based on the maintained value ET and the output TONR will be on when ET is greater than or equal to the
preset value PT. After ET reaches PT value, the timing will not be stopped till ET reaches maximum
4294967295.
When EN is off, the current value ET of the timer is cleared as 0 and the output bit is reset.
Explanation of input and output parameter of the instruction:
Parameter
name
Explanation
Data
type
Available
device
EN
The execution condition of this instruction.
“TONR_ms” instruction is executed as “EN” turns on; the
output “TON” is reset and the current value “ET” is
cleared as 0 as “EN” turns off.
BOOL M,I,Q, constant
IN
As “IN” is on, the timer starts timing; as “IN” is off, the
current value “ET” is maintained.
BOOL M,I,Q, constant
PT Preset value of the timer UDINT Constant,D
TONR
The current value “ET” is greater than or equal to the
prest value PT, “TONR” is on.
BOOL M,Q
ET The current value of the timer. UDINT D
Note: For the sequence chart of TONR_ms, please refer to the program example of TONR_s.