4. Motion Control Instruction
4-122 DVP-MC operating manual
4.6.36. MOV_BW
API
Controller
163
MOV_BW
Move multiple bit device values to
multiple registers
10MC11T
Explanation of the instruction:
MOV_BW is used for sending multiple bit device values to the word devices.
When EN is on, the bit device data with S1 as the starting bit device data is sent to the register zone with D as
the starting register and the bit device length is specified by S2. When the data length S2 is larger than
maximum 64, it is counted as 64. And the part above 64 is invalid.
Explanation of input and output parameter of the instruction:
Parameter
name
Explanation
Data
type
Available
device
EN “MOV_BW” is executed as “EN” turns on. BOOL M,I,Q, constant
S1 The source where the data comes from. BOOL M,I,Q
S2
The length of the bit device of the transmitted zone, the
max value for S2 is 64.
UINT Constant,D
D The starting register of the target zone INT D
Note: If the bit device of the instruction exceeds the range of that of the controller, only the data in the bit
device within the valid range can be sent.