4. Motion Control Instruction
4-124 DVP-MC operating manual
4.6.38. ZCP
API
Controller
165
ZCP
Compare 16-bit integer to the
values in one zone
10MC11T
Explanation of the instruction:
ZCP is used for comparison of one 16-bit signed integer with one zone.
When EN is on, S is within the range from Low value to High value, Q=On and nQ=Off; if S value is out of the
range from Low value to High value, nQ =On and Q=Off;
When EN is Off, the status of Q and nQ keeps unchanged.
Explanation of input and output parameter of the instruction:
Parameter
name
Explanation
Data
type
Available
device
EN “ZCP” is executed as “EN” turns on. BOOL M,I,Q, constant
S The compared value INT Constant,D
Low The lower limit for zone comparison INT Constant,D
High The high limit for zone comparison INT Constant,D
Q
As the instruction is executed and Low≤S ≤High, the “Q”
bit is on.
BOOL M,Q
nQ
As the instruction is executed and High<S or S<Low,
the “nQ” bit is on.
BOOL M,Q