2. System Function
2-10 DVP-MC operating manual
Special
D
Function explanation Attribute Data type latched Remark
D6508
The check code of
exchanged data
when PLC => MC
R UINT N
The check code of the data
which PLC writes to MC.
D6509
Setting of
RUN/STOP switch
R/W UINT N
1. When D6509 value = 0
RUN/STOP switch is
disabled.
2. When D6509 value = 1,
RUN/STOP switch is
enabled.
D6511
Low word of
DVP10MC status
word
R UINT N
D6512
High word of
DVP10MC status
word
R UINT N
Status word of MC module
D6513
Low word of
feedback pulse
number of the
encoder
D6514
High word of
feedback pulse
number of the
encoder
R UDINT N
Feedback pulse number of the
encoder
6515
Motion program
RUN/STOP and
system reset
R/W UINT N
7: Program is being executed.
0: Execution of program stops
16: System reset which is
equivalent to that 10MC is
powered on again.
When the motion control
program of 10MC is running,
write 0 to D6515 to stop the
program being executed.
Afterwards, the motion control
program can not be executed
again unless 7 is written to
D6515 after pressing the
Reset key.
Page view 17