Appendix A
DVP-MC operating manual A-3
Table 1
D1036 or
D1120 bit no.
Explanation Communication format setting
b0 Data length b0=0: 7 b0=1: 8
b2, b1=00 : None
b2, b1=01 : Odd
b2, b1 Parity bit
b2, b1=11 : Even
b3 Stop bit b3=0:1 bit b3=1:2 bit
b7~b4=0001(H1) : 110bps
b7~b4=0010(H2) : 150bps
b7~b4=0011(H3) : 300bps
b7~b4=0100(H4) : 600bps
b7~b4=0101(H5) : 1200bps
b7~b4=0110(H6) : 2400bps
b7~b4=0111(H7) : 4800bps
b7~b4=1000(H8) : 9600bps
b7~b4=1001(H9) : 19200bps
b7~b4=1010(HA) : 38400bps
b7~b4=1011(HB) : 57600bps
b7~b4 Baud rate
b7~b4=1100(HC) : 115200bps
b8
Selection of the start
character
b8=0: none b8=1: D1124
b9
Selection of the first
end character
b9=0: none b9=1: D1125
b10
Selection of the
second end
character
b10=0: none b10=1: D1126
b15~b11 Undefined
Explanation of relevant special M for communication at COM1 port :
Special M
no.
Function Remark
M1139
Selection of
ASCII/RTU mode
M1139=On, communication mode is RTU
M1139=Off, communication mode is RTU
M1138
Communication
format is retained
When M1138=On, Change the value of D1036, but the
communication format of COM1 is unchanged.
Explanation of relevant special M when COM2 port is possessed by motion control module:
Special M
no.
Function Remark
M1143
Selection of
ASCII/RTU mode
M1143=On, communication mode is RTU.
M1143=Off, communication mode is ASCII.
M1120
Communication
format is retained
When M1120=On, Change the value of D1120, but the
communication format of COM2 is unchanged.