Appendix A
DVP-MC operating manual A-23
Data structure of response message:
Data order Name Byte
Byte0 Modbus ID Single byte
Byte1 Function code Single byte
Byte2 High byte
Byte3
The start address of DVP10MC11T bit device where to write the
value
Low byte
Byte4 High byte
Byte5
The number of DVP10MC11T bit devices where to write the value
Low byte
Byte6 Low byte of CRC check sum Low byte
Byte7 High byte of CRC check sum High byte
Data structure of abnormality response message:
Data order Name Byte
Byte0 Modbus ID Single byte
Byte1 0x80+ function code Single byte
Byte2 Abnormality response code High byte
Byte3 Low byte of CRC check sum Low byte
Byte4 High byte of CRC check sum High byte
Note: How many bytes of data in request message are determined by the number of bit device where to
write the value in the response message.
¾ Set DVP10MC11T M0~M7=1000 0001, M8~M15=0001 1000, M16~M19=0110 via function code 0F;
M0 address: 0x0800
Request message: “01 0F 08 00 00 14 03 81 18 06 8B F9”
Response message: “01 0F 08 00 00 14 57 A4”
The Indication of Modbus Communication Port LED
COM1 LED is RS-232 communication port indicator used by PLC module to show RS-232
communication state.
LED state Indication
Yellow light flash There are response data at RS-232COM1port.
Off There are no response data at RS-232COM1port.
COM2 LED is RS-485 communication port indicator commonly used by motion control
module and PLC module to show RS-485 communication state.
RUN state Indication
Yellow light flash
There are response data at RS-485COM2port
Off There are no response data at RS-485COM2port