Chapter 1 Introduction| BLD-E1 Series Revision May 2009, 00DE, V0.50
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-59Positive torqueReverse03-00~0 2=7Positive torque limit03-00~0 2=8Negative t
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-60 Revision May 2009, 00DE, V0.50 03-07 Positive/negative Bias Mode (ACI) (can be set to
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-6103-12 Analog Input Delay Time (VR) Control mode VF VFPG FOCPM Fac
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-62 Revision May 2009, 00DE, V0.50 Group 4 Multi-Step Speed Parameters This parameter
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-63Group 5 IM Parameters This parameter can be se
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-64 Revision May 2009, 00DE, V0.50 Group 6 Protection Parameters This
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-6506-02Over-CurrentDetectionLevelOutput FrequencyOver-Current Stallprevention
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-66 Revision May 2009, 00DE, V0.50 It is used to set the accel./decel. time selection wh
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-67 06-10 Over-torque Detection Time (OT2) Control mode VF VFPG FOCPM
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-68 Revision May 2009, 00DE, V0.50 The parameter is set by the output frequency, current
Chapter 1 Introduction|BLD-E1 Series 1-4 Revision May 2009, 00DE, V0.50Internal Structure ACI/AVI NPN/PNPRS485 port (RJ-45)Digital keypadExternal ter
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-69 06-16 Present Fault Record 06-17 Second Most Recent Fault Record 06-18 Thi
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-70 Revision May 2009, 00DE, V0.50 28 Reserved 29 Reserved 30 Memory write-in er
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-71 59 PU time-out (cP10) It will record when the fault occurs and forc
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-72 Revision May 2009, 00DE, V0.50 Group 7 Special Parameters This pa
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-73ONOFF01-0907-05Output freque ncyRun /StopTimeDC Brake TimeDC Brake Timeduri
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-74 Revision May 2009, 00DE, V0.50 07-14 Maximum Torque Command Control mode FOCPM
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-7507-22 Middle Torque Offset Control mode FOCPM Factory Setting: 20
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-76 Revision May 2009, 00DE, V0.50 07-28 Emergency Stop (EF) & Forced Stop Selection
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-77Group 8 PM Parameters This parameter can be set
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-78 Revision May 2009, 00DE, V0.50 NOTE The rated speed can’t be larger or equal to 120f
Chapter 1 Introduction| BLD-E1 Series Revision May 2009, 00DE, V0.50
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-79 It is used to set the rated speed of the motor and need to set according
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-80 Revision May 2009, 00DE, V0.50 08-10 Magnetic Pole Re-orientation Control mode FOCPM
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-81Group 9: Communication Parameters This parameter can be set during o
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-82 Revision May 2009, 00DE, V0.50 09-04 Communication Protocol Control mode VF VFPG FO
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-83 2. Data Format 10-bit character frame (For ASCII): ( 7.N.2)( 7.E.1)Star
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-84 Revision May 2009, 00DE, V0.50 RTU mode: START A silent interval of more than 10 ms Ad
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-85Command message: Response message: LF RTU mode: Command message: Res
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-86 Revision May 2009, 00DE, V0.50 ASCII Mode: Command message: Response message: STX ‘:
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-873.4 Check sum ASCII mode: LRC (Longitudinal Redundancy Check) is calculated
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-88 Revision May 2009, 00DE, V0.50 Step 5: Repeat step 3 and 4 until eight shifts have been
Chapter 1 Introduction|BLD-E1 Series 1-6 Revision May 2009, 00DE, V0.50TN-S grounding system: TN-S is a grounding system with 3-phase, 4-line and PE
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-89Content Address Function Bit 4-5 00B: No function 01B: FWD 10B: REV 11B
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-90 Revision May 2009, 00DE, V0.50 Content Address Function 2120H Frequency command wh
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-91‘0’ Exception code ‘2’ ‘7’ LRC CHK Low LRC CHK High ‘7’
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-92 Revision May 2009, 00DE, V0.50 Group 10 Speed Feedback Control Parameters This paramet
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-93 2 Phase B leads in a forward run command and phase A leads in a reverse r
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-94 Revision May 2009, 00DE, V0.50 This parameter determines the maximum encoder feedback
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-95UVPr.10-10=1Pr.10-10=0Z SignalZ Signal 10-11 ASR (Auto Speed Regulation)
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-96 Revision May 2009, 00DE, V0.50 Control mode VF VFPG FOCPM Factory Setting: 84 Se
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-97Control mode VFPG FOCPM Factory Setting: 60 Settings 0 to 4800rpm
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-98 Revision May 2009, 00DE, V0.50 Group 11 Advanced Parameters This paramet
Chapter 1 Introduction| BLD-E1 Series Revision May 2009, 00DE, V0.50
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-9911-14 Reserved 11-15 Reserved 11-16 PDFF Gain Value Control mode VF
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-100 Revision May 2009, 00DE, V0.50 Group 12 User-defined Parameters This paramete
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-10112-07 Output Voltage at Present Fault Control mode VF VFPG FOCPM
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-102 Revision May 2009, 00DE, V0.50 Setting 2143 12-15 Second Most Recent Fault Record
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-10312-22 Fourth Most Recent Fault Time of Motor Operation (min.)Control mod
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-104 Revision May 2009, 00DE, V0.50 12-29 Sixth Most Recent Fault Time of Motor Operation
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-105Group 13 View User-defined Parameters This parameter can be set during op
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-106 Revision May 2009, 00DE, V0.50 This page intentionally left blank
Revision May 2009, 06EE, V0.50 5-1 Chapter 5 Troubleshooting 5.1 Over Current (OC) oc Over-current during constant speedCheck if there
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 5-2 Revision May 2009, 00DE, V0.50 5.2 Ground Fault GFFGr ound faul tNoYesIs output circui
Chapter 1 Introduction|BLD-E1 Series 1-8 Revision May 2009, 00DE, V0.501.1.5 Remove Instructions 1.2 Preparation for Installation and Wiring 1.2.1 Am
| BLD-E1 Series Revision May 2009, 00DE, V0.50 5-35.4 Low Voltage (Lv) Low voltageIs input power correct? Or power cut, including momentary power l
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 5-4 Revision May 2009, 00DE, V0.50 5.5 Over Heat (oH1) Brushless DC motor drive overheatsH
| BLD-E1 Series Revision May 2009, 00DE, V0.50 5-55.7 Keypad Display is Abnormal Abnormal display or no displayCycle power to brushless DCmotor dr
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 5-6 Revision May 2009, 00DE, V0.50 5.9 Motor cannot Run Motor cannot run Check if keypad
| BLD-E1 Series Revision May 2009, 00DE, V0.50 5-75.10 Motor Speed cannot be Changed Motor can run butcannot change speedYesYesYesYesYesY
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 5-8 Revision May 2009, 00DE, V0.50 5.11 Motor Stalls during Acceleration Motor stalls during
| BLD-E1 Series Revision May 2009, 00DE, V0.50 5-95.12 Electromagnetic/Induction Noise Many sources of noise surround brushless DC motor drives and
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 5-10 Revision May 2009, 00DE, V0.50 4. Store within a relative humidity range of 0% to 90%
Revision May 2009, 00DE, V0.50 6-1 Chapter 6 Fault Code Information and Maintenance 6.1 Fault Code Information The brushless DC motor drive has a co
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series 6-2 Revision May 2009, 00DE, V0.50 6.1.1 Common Problems and Solutions Fault Name Fau
Chapter 1 Introduction| BLD-E1 Series Revision May 2009, 00DE, V0.50
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series Revision May 2009, 00DE, V0.50 6-3Fault Name Fault Descriptions Corrective Actions
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series 6-4 Revision May 2009, 00DE, V0.50 Fault Name Fault Descriptions Corrective Actions
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series Revision May 2009, 00DE, V0.50 6-5Fault Name Fault Descriptions Corrective Actions
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series 6-6 Revision May 2009, 00DE, V0.50 Fault Name Fault Descriptions Corrective Actions
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series Revision May 2009, 00DE, V0.50 6-7Fault Name Fault Descriptions Corrective Actions
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series 6-8 Revision May 2009, 00DE, V0.50 Voltage Maintenance Period Check Items Methods an
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series Revision May 2009, 00DE, V0.50 6-9If machine or insulator is deformed, cracked, dama
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series 6-10 Revision May 2009, 00DE, V0.50 Maintenance Period Check Items Methods and Crite
Chapter 6 Fault Code Information and Maintenance| BLD-E1 Series Revision May 2009, 00DE, V0.50 6-11Maintenance Period Check Items Methods and Crite
Chapter 1 Introduction|BLD-E1 Series 1-10 Revision May 2009, 00DE, V0.505. The heat sink temperature may rise to 90°C when running. The material on
Revision May 2009, 00DE, V0.50 A-1 Appendix A Specific
Appendix A Specifications| BLD-E1 Series A-2 Revision May 2009, 00DE, V0.50 Voltage Class 460V Class Model Number BLD-XXXE1 004 007 015 022 037 M
Appendix B Accessories| BLD-E1 Series Revision May 2009, 00DE, V0.50 A-3General Specifications Operation Functions Built-in AVR, over-voltage/over-cu
Appendix A Specifications| BLD-E1 Series A-4 Revision May 2009, 00DE, V0.50 This page intentionally left blank
Revision May 2009, 00DE, V0.50 B-1 Appendix B Accessor
Appendix B Accessories| BLD-E1 Series B-2 Revision May 2009, 00DE, V0.50 NOTE 1. If damage to the drive or other equipment is due to the fact that t
Appendix B Accessories| BLD-E1 Series Revision May 2009, 00DE, V0.50 B-3B.1.1 Dimensions and Weights for Brake Resistors (Dimensions are in millimete
Appendix B Accessories| BLD-E1 Series B-4 Revision May 2009, 00DE, V0.50 Order P/N: BR500W030, BR500W100, BR1KW020, BR1KW075 Model no. L1 L2 H D
Appendix B Accessories| BLD-E1 Series Revision May 2009, 00DE, V0.50 B-5 Order P/N: BR1K0W050, BR1K2W008, BR1K2W6P8, BR1K5W005, BR1K5W040
Appendix B Accessories| BLD-E1 Series B-6 Revision May 2009, 00DE, V0.50 B.2 No-fuse Circuit Breaker Chart For 1-phase/3-phase drives, the current ra
Chapter 1 Introduction| BLD-E1 Series Revision May 2009, 00DE, V0.50
Appendix B Accessories| BLD-E1 Series Revision May 2009, 00DE, V0.50 B-7B.3 Fuse Specification Chart Smaller fuses than those shown in the table are
Appendix B Accessories| BLD-E1 Series B-8 Revision May 2009, 00DE, V0.50 B.4 AC Reactor B.4.1 AC Input Reactor Recommended Value 230V, 50/60Hz, 1-Pha
Appendix B Accessories| BLD-E1 Series Revision May 2009, 00DE, V0.50 B-9Inductance (mH) kW HP Fundamental Amps Max. continuous Amps 3% impedance 5%
Appendix B Accessories| BLD-E1 Series B-10 Revision May 2009, 00DE, V0.50 Application 2 Question Silicon rectifier and brushless DC motor drive are
Appendix B Accessories| BLD-E1 Series Revision May 2009, 00DE, V0.50 B-11B.5 Zero Phase Reactor (RF220X00A) Dimensions are in millimeter and (inch)
Appendix B Accessories| BLD-E1 Series B-12 Revision May 2009, 00DE, V0.50 B.6 DIN Rail Dimensions This is only applicable for frame A. As for frame
Chapter 1 Introduction|BLD-E1 Series 1-12 Revision May 2009, 00DE, V0.501.3 Dimensions (Dimensions are in millimeter and [inch]) Frame A W1H1WHDS2S1D
Preface Thank you for choosing DELTA’s multi-function BLD-E1 Series. The BLD-E1 Series is manufactured with high-quality components and materials an
Revision May 2009, 00DE, V0.50 2-1 Chapter 2 Installation and Wiring After removing the cover of input/output terminals and control terminals, check
Chapter 2 Installation and Wiring| BLD-E1 Series 2-2 Revision May 2009, 00DE, V0.502.1 Wiring There are main circuit and control circuit for the wiri
Chapter 2 Installation and Wiring| BLD-E1 Serie
Chapter 2 Installation and Wiring| BLD-E1 Series 2-4 Revision May 2009, 00DE, V0.50Figure 3 Wiring for NPN mode and PNP mode NOTEFactorysettingNPNPNP
Chapter 2 Installation and Wiring| BLD-E1 Serie
Chapter 2 Installation and Wiring| BLD-E1 Series 2-6 Revision May 2009, 00DE, V0.502.2 External Wiring Items Explanations Power supply Please follo
Chapter 2 Installation and Wiring| BLD-E1 Serie
Chapter 2 Installation and Wiring| BLD-E1 Series 2-8 Revision May 2009, 00DE, V0.50 When using a general GFCI (Ground Fault Circuit Interrupter), s
Chapter 2 Installation and Wiring| BLD-E1 Serie
Chapter 2 Installation and Wiring| BLD-E1 Series 2-10 Revision May 2009, 00DE, V0.502.4 Control Terminals Terminal symbols and fu
WARNING! Never connect the output terminals U/T1, V/T2, and W/T3 of brushless DC motor drive directly to the AC mains circuit power supply. DO
Chapter 2 Installation and Wiring| BLD-E1 Serie
Chapter 2 Installation and Wiring| BLD-E1 Series 2-12 Revision May 2009, 00DE, V0.50Terminal Symbol Terminal Function Factory Settings (NPN mode) ON:
Chapter 2 Installation and Wiring| BLD-E1 Serie
Chapter 2 Installation and Wiring| BLD-E1 Series 2-14 Revision May 2009, 00DE, V0.50This page intentionally left blank
Revision May 2009, 00DE, V0.50 3-1 Chapter 3 Keypad and Start Up 3.1 Keypad 3.2 Operation Method 3.3 Trial Run Make sure that the wiring is
Chapter 3 Keypad and Start Up| BLD-E1 Series 3-2 Revision May 2009, 00DE, V0.503.1 Keypad LED DisplayIn dicate speed, volta ge, curre nt a nduser d
Chapter 3 Keypad and Start Up| BLD-E1 Series
Chapter 3 Keypad and Start Up| BLD-E1 Series 3-4 Revision May 2009, 00DE, V0.503.1.1 How to Operate the Digital Keypad The setting values in the fo
Chapter 3 Keypad and Start Up| BLD-E1 Series
Chapter 3 Keypad and Start Up| BLD-E1 Series 3-6 Revision May 2009, 00DE, V0.503.2 Operation Method The operation method can be set via communicati
Table of Contents Preface ... i Table of C
Chapter 3 Keypad and Start Up| BLD-E1 Series
Chapter 3 Keypad and Start Up| BLD-E1 Series 3-8 Revision May 2009, 00DE, V0.50 3.3 Trial Run The factory setting of trial run is by the potentiome
Revision May 2009, 06EE, V0.50 4-1 Chapter 4 Parameters The BLD-E1 parameters are divided into 14 groups by property for easy setting. In most appli
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-2 Revision May 2009, 00DE, V0.50 4.1 Summary of Parameter Settings Group 00 System Paramet
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-3Parameter Explanation Settings Factory Setting VF VFPG FOCPM5:defined by
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-4 Revision May 2009, 00DE, V0.50 Parameter Explanation Settings Factory Setting VF VFPG
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-5Parameter Explanation Settings Factory Setting VF VFPG FOCPMRegulation (A
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-6 Revision May 2009, 00DE, V0.50 Group 01 Basic Parameters : The par
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-7Parameter Explanation Settings Factory Setting VF VFPG FOCPM01.18 Accel T
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-8 Revision May 2009, 00DE, V0.50 Group 02 Digital
Chapter 3 Keypad and Start Up...3-1 3.1 Keypad...
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-9Parameter Explanation Settings Factory SettingVF VFPG FOCPM13~14: Reserved
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-10 Revision May 2009, 00DE, V0.50 Parameter Explanation Settings FactorySettingVF VFPG F
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-11Parameter Explanation Settings Factory SettingVF VFPG FOCPM25: Forward ru
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-12 Revision May 2009, 00DE, V0.50 Group 03: Time Parameters : The para
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-13ParameterExplanation Settings Factory Setting VF VFPG FOCPM03.13 Analog In
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-14 Revision May 2009, 00DE, V0.50 Group 04: Multi-Step Speed Parameters : The paramete
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-15Group 05: IM Parameters : The parameter can be set duri
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-16 Revision May 2009, 00DE, V0.50 Group 6: Protection Parameters : The parameter can
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-17ParameterExplanation Settings Factory Setting VF VFPG FOCPMDetection Time (
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-18 Revision May 2009, 00DE, V0.50 ParameterExplanation Settings Factory Setting VF VFPG FO
Chapter 1 Introduction| BLD-E1 Series 6.1.2 Reset ...
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-19ParameterExplanation Settings Factory Setting VF VFPG FOCPM29: Reserved 30:
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-20 Revision May 2009, 00DE, V0.50 Group 07 Protection Parameters : The parameter can be s
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-21Parameter Explanation Settings FactorySettingVF VFPG FOCPM07.19 Source o
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-22 Revision May 2009, 00DE, V0.50 Group 08 PM Parameters : The parame
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-23Group 09 Communication Parameters : The parameter can be set during ope
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-24 Revision May 2009, 00DE, V0.50 Group 10: Speed Feedback Control Parameters : The param
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-25 ParameterExplanation Settings Factory Setting VF VFPG FOCPM10.09 Encoder
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-26 Revision May 2009, 00DE, V0.50 ParameterExplanation Settings Factory Setting VF VFPG FO
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-27Group 11: Advanced Parameters : The parameter can be set during op
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-28 Revision May 2009, 00DE, V0.50 Group 12: User-defined Parameters (User-defined Paramete
This page intentionally left blank
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-29Parameter Explanation Settings FactorySettingVF VFPG FOCPM12.13 Multi-fun
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-30 Revision May 2009, 00DE, V0.50 Parameter Explanation Settings FactorySettingVF VFPG FO
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-31Parameter Explanation Settings FactorySettingVF VFPG FOCPMOperation (min.)
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-32 Revision May 2009, 00DE, V0.50 Group 13: View User-defined Parameters : The parameter
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-334.2 Description of Parameter Settings Group 00 User Parameters
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-34 Revision May 2009, 00DE, V0.50 00-02 Parameter Reset Control mode VF VFPG FOCPM
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-3500-04 Content of Multi-Function Display 10 Display the electrical ang
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-36 Revision May 2009, 00DE, V0.50 0: OFF, 1: ON MI3: Pr.02-01 is set to 1 (multi-step spee
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-37 Ramp to stop: the brushless DC decelerates the motor to Minimum Outpu
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-38 Revision May 2009, 00DE, V0.50 This parameter determines the control method of the br
Revision May 2009, 00DE, V0.50 1-1 Chapter 1 Introduction The brushless DC motor drive should be kept in the shipping carton or crate before install
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-39temperature, carrier frequency will be lowered to 10kHz, moreover, overload
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-40 Revision May 2009, 00DE, V0.50 2K (Pr. 00-12 = 2) 900rpm 3K (Pr. 00-12 = 3) 1350rpm 4
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-41 BLE-E1 series is shipped without digital keypad and users can use extern
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-42 Revision May 2009, 00DE, V0.50 Group 01 Basic Parameters This par
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-4301-03 2nd Output Frequency Setting Control mode VF VFPG Factory sett
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-44 Revision May 2009, 00DE, V0.50 01-05 01-03 01-0101-0601-0401-0201-0001-0701-0801-0901-1
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-4501-12 Accel. Time 1 Factory setting: 3.0001-14 Accel. Time 2 Factory s
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-46 Revision May 2009, 00DE, V0.50 01-23 Switch Frequency between 1st/4th Accel/decel Fa
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-47Frequency01-12accel. time01-13decel. timeTime01-25=S201-26=S301-24=S101-27=
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-48 Revision May 2009, 00DE, V0.50 Group 2 Digital Input/Output Parameters This paramete
Chapter 1 Introduction|BLD-E1 Series 1-2 Revision May 2009, 00DE, V0.501.1 Receiving and Inspection This BLD-E1 brushless DC motor drive has gone thr
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-4902-01 Multi-Function Input Command 3 (MI3) Factory Setting: 102-02 Mu
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-50 Revision May 2009, 00DE, V0.50 Settings VF VFPG FOCPM 33: Low torque bias (by Pr.07-23)
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-51Settings Functions Descriptions 8 The 1st, 2nd acceleration or decelerati
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-52 Revision May 2009, 00DE, V0.50 Settings Functions Descriptions 27 ASR1/ASR2 selection
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-5302-09 Digital Input Response Time Control mode VF VFPG FOCPM Fact
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-54 Revision May 2009, 00DE, V0.50 3:Desired frequency attained 1 (Pr. 02-25, 02-26) ○ ○
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-55 Settings Functions Descriptions 0 No Function 1 AC Drive Operational
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-56 Revision May 2009, 00DE, V0.50 Settings Functions Descriptions 22 Over-current Stall
Chapter 4 Parameters| BLD-E1 Series Revision May 2009, 00DE, V0.50 4-57when the drive is running and OFF when the drive is stop; if multi-function
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series 4-58 Revision May 2009, 00DE, V0.50 Group 3 Analog Input/Output Parameters This parameter