Delta 20-140 User Manual

Browse online or download User Manual for Circular saws Delta 20-140. RE88865175

  • Download
  • Add to my manuals
  • Print
  • Page
    / 5
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Mar 9, 2013
1
Product data sheet
Characteristics
RE88865175
time delay relay for star-delta starter - 20..140
ms - 24..240 V AC - 1 contact
Main
Range of product Zelio Time
Product or component
type
Industrial timing relay
Contacts type and com-
position
Timed contact, AgNi (cadmium free)
Component name RE88865
Time delay type Q
Time delay range 1 h
1 min
1 s
10 h
10 min
10 s
100 h
[Us] rated supply volt-
age
24...240 V AC 50/60 Hz
24 V DC
Complementary
Discrete output type Relay
Width pitch dimension 22.5 mm
Non-overlap time 100 ms
120 ms
140 ms
20 ms
40 ms
60 ms
80 ms
Voltage range 0.85...1.1 Us
Connections - terminals Screw terminals, clamping capacity: 2 x 2.5 mm² without cable end
Screw terminals, clamping capacity: 2 x 1.5 mm² with cable end
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Minimum pulse duration 30 ms
100 ms under load
Maximum reset time 100 ms on de-energisation
On-load factor 100 %
Maximum power consumption 32 VA 240 V
Maximum power consumption 1.5 W 240 V
0.6 W 24 V
Breaking capacity 2000 VA
Breaking capacity 80 W
Minimum switching current 10 mA
Maximum switching current 8 A
Maximum switching voltage 250 V
Electrical durability 100000 cycles 8 A at 250 V resistive
Mechanical durability 5000000 cycles
[Uimp] rated impulse withstand voltage 5 kV for 1.2...50 µs conforming to IEC 61812-1
5 kV for 1.2...50 µs conforming to IEC 60664-1
Marking CE
Creepage distance 4 kV/3 conforming to IEC 60664-1
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - RE88865175

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products conta

Page 2 - Contractual warranty

2Surge withstand 2 kV (common mode) conforming to IEC 61000-4-5 level 31 kV (differential mode) conforming to IEC 61000-4-5 level 3Mounting support 35

Page 3

3Product data sheetTechnical DescriptionRE88865175Function Q: Star-Delta StartingDescriptionOn energisation, the star contact closes instantaneously d

Page 4

4Product data sheetDimensions DrawingsRE88865175Width 22.5 mm

Page 5

5Product data sheetConnections and SchemaRE88865175Wiring Diagram