10Notes on installationThe weatherproofed KGW 630-1000 air-coinditioning units have a UV-resistant,weatherproof skinned roof.Fully assembled units are
11Notes on installationThe fan shaft must always be horizontal.Remember to remove the transportation locking devices of fans mounted onvibration dampe
12When installing, take care to ensure that no dirt or other foreign matter penetrates insidethe washer.The water used for the washer under normal con
13CautionConnection to electricity supplyThe air-conditioning unit must be wired by a trained, qualified electrician inaccordance with the applicable
14Connecting to electricity supplyWiring for single-speed driveMotors up to 2.2 kW usually have direct startup,whereas a star-delta circuit is usual a
15CautionCautionInitial operationWait until the fan or fans run down to a complete standstill before you open theinspection door.Check that safety dev
16Air conditioner KG 15 20 25F 40F 40 63 100-1000Min. air flow (m³/h)550* 900 900 1600 1600 2500depends onhorizontal + vertical é designMin. air flow
17CautionInitial operationBefore filling the chiller system with refrigerant, adopt suitable measures to ensurethat no traces of moisture are left in
18CautionCautionMaintenanceBefore starting maintenance work, always switch off the main switch and repairswitch(es) and lock them in the OFF position.
19CautionCautionMaintenance / Frost protectionThe washer and drip separator must be cleaned at regular intervals. The cleaningcycle depends on the ope
2ContentsContents ... PageWarnings / Notes on safety ...
20Designation of equipment Airconditioning units for indoor installationAirconditioning units for outdoor installationAirconditioning units with indir
3These Installation and Maintenance Instructions apply only to WOLF KG and KGWStandard air-conditioning units.The persons charged with the installatio
4The standards and regulations applicable to the KG 15-250 Standard series andthe KG/KGW 630-1000 series air-conditioning units are as follows:- EC Di
5Delivery to site / TransportationDelivery to siteTransportClearancesKG 15-250 and KG/KWG 630-1000 series air conditioners are delivered to site intra
6Notes on installationFoundation Install the units and components on a surface which is smooth, level and ofadequate load-bearing strength.The base fr
7KG and KGW configurations incorporating a washer section require a base frameor foundation lower at the floor of the washer unit than elsewhere, beca
8Notes on installationSecuring the sections Sections with angle-section frames (KG 40-250) are secured by means of M6threaded fasteners and clip spac
9Notes on installationConfigurations:stacked or side-by-sideSections for stacked configurations are delivered to site separately and must besecured to