Chapter 4 Parameter Settings|DD Series
4-42
10
OD command Active when the operation direction is door open.
11
CD command Active when the operation direction is door close.
12
Demo Indication Active when the drive is in demo mode.
13
Demo complete Active when each time door open/close is complete in demo
mode (contact closed for 0.5s only).
14
Emergency stop indication Active when emergency stop is detected.
15
Force stop indication Active when force stop is detected.
16
Door open complete (limit)
signal output
Active when position mode (Pr.06-11) is set to “no door close
limit signal” and the door width is greater than the setting in
Pr.04-06.
Active when position mode (Pr.06-11) is set to door close limit
signal allow and one of MI (Pr.02-01~02-05) is set to 14.
17
Door close complete (limit)
signal output
Active when position mode (Pr.06-11) is set to “no door close
limit signal” and the door width is less than Pr.05-06 setting
during the door close.
Active when position mode (Pr.06-11) is set to door close limit
signal allow and one of MI (Pr.02-01~02-05) is set to 15.
18
Door close error Active when door close error. (Includes door reopen and not
reopen).
19
Position complete signal Active when positioning is completed after drive power is on or
PGEr. This function is valid when Pr.00-10=00.
20
Position Detection 1(for door
close only)
Active when door close width is lower than Pr.06-14 (valid when
door close).
21
Position Detection 2(for door
close only)
Active when door close width is lower than Pr.06-15 (valid when
door close).
22
Position Detection 3(for door
close only))
Active when door close width is lower than Pr.06-16 (valid when
door close).
23
Position Detection 1(for door
open only)
Active when door close width is lower than Pr.06-14 (valid when
door open).
24
Position Detection 2(for door
open only)
Active when door close width is lower than Pr.06-14 (valid when
door open).
25
Position Detection 3(for door
open only)
Active when door close width is lower than Pr.06-14 (valid when
door open).
26
PG feedback error Active when PG feedback signal error is detected
27
output signal when unable to
open the door
28
over torque (OT1)
Digital Output Direction
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 0
Settings
0065535
This parameter is set via bit setting. If a bit is 1, the corresponding output acts in the opposite way.
Example:
If Pr02-08=1 (operation indication) and Pr.02-13=0, Relay 1 RA-RC is closed when the drive runs and is
open when the drive is stopped.
If Pr02-08=1 and Pr02-13=1, Relay 1 RA-RC is open when the drive runs and is closed when the drive is
stopped.
Position Detection Signal 1
Control mode
VF
VFPG SVC FOCPG FOCPM
Factory setting: 25.0
Settings 0.0~100.0%
Position Detection Signal 2