Chapter 4 Parameter Settings|DD Series
4-55
Larger current is required at the beginning of door open and door close, so it needs to have larger
re-open current level in the acceleration area. Please refer to the following figure for setting reopen
current and acceleration area:
Door Close
Holding Speed
Open Door ( REV
)
Close Door (FWD)
04.00
Door Open
Speed
by Initial
04.08
Door Open
Acceleration
Time 1
04.0 9
Door Open
Deceleration
Time 1
04.03
Door Open High Speed 1
04.05
Door Open
Final Speed
04.01
Door Open Distance by
Ini tial Speed
04.04
Door Open
by Final Speed
B e gi ns
04.06
Door Open
by Holding Speed
B e gi ns
04.07
Door Open
Holding Speed
05.03
Door Close
High Speed 1
05. 08
Door Close
Ac ce lera ti on Time 1
05.05
05.04
05.06
Door Close
by Holding
Speed
Begins
05.07
05.09
05.01
Door Close
Dis tance by
Ini tial Speed
05.00
Door Close
Initial Speed
Door Close
Final Speed
Door Close
Final Speed
Door Close
by Final Speed
B e gi ns
Door Open Limit
100. 0%
Re-open Detected Area
Door Close Limit
0.0%
05.25
Door reopen current level 1
05.25 * 04.11/100
Door Re-open Current Level
for Acceleration Area
05 .32
Door Re-open
Acceleration
Boundary
05. 31
Door Re-open
Low Speed Boundary
Door Close Error Deceleration Time
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 0.4
Settings 0.1~3600sec
Door Re-open Detection Time
Control mode VF VFPG SVC FOCPG FOCPM
Factory setting: 0.2
Settings 0~10.0sec