7.4.10.3 Test Analog Voltage Output
Figure 61: Test Analog Outputs Menu
The Test Output screen, as shown in Figure 62, is used to calibrate the analog recorder
output. When the Test Output screen is selected, the NEXT key is used to move to the
percentage field where the arrow keys ( and ) are used to choose the appropriate
setting. The NEXT key is then used to move to the Apply field where the Enter key is hit
to set the analog output to the selected value. The analog output response should match the
value that was entered. For example, if 80 percent is entered for the percent full scale level,
and the analog output is set for 0 to 10 VDC, the analog output is 8.000 VDC. This process
can be repeated as often as needed. When done, the NEXT key is used to move to the
Done field and the Enter key is hit to leave the screen. The condition of the analog output
before the test is restored when the test is concluded. See the section on analog outputs
found on page 32 for additional information.