Appendix A Module Settings
Appendix A discusses the necessary settings for 2 gateway modules. The 1785-KE
module, Series A and B, and the 1771-KE and 1771-KF modules.
A.1 1785-KE Module (Series A) Switch Settings
The 1785-KE module (Series A) has 6 switch assemblies which allow the selection of
various communications options. The 1785-KE Module RS-232 parameters should be set
up as follows:
· Full duplex
· Same parity as configured for the DeltaV PSIC Port
· BCC error checking
· Data Highway Plus communications baud rate of 57.6 K
· RS-232C communications baud rate same as DeltaV PSIC port
· Execute diagnostic commands
There are additional switches on the 1785-KE module (Series A) which may require
adjustment. Refer to the Allen-Bradley User Manual for further information.
· SW1 - RS-232C link
· SW2 - Not used (Switches must be off)
· SW3/SW4 - Node Number
· SW5 - Network link communication baud rate
· SW6 - RS232C link communication rate and diagnostic commands
A.2 1785-KE Module (Series B) Switch Settings
The 1785-KE (Series B) has 4 switch assemblies which allow the selection of various
communications options. The 1785-KE Module RS-232C parameters should be defined
as follows:
· Full duplex
· Same parity as configured for the DeltaV PSIC port
· BCC error checking
· Data Highway Plus communications baud rate of 57.6K
· RS-232C communications baud rate same as configured for DeltaV PSIC port
· Execute diagnostic commands