PD-01 PROFIBUS-DP Module
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
26
Item Name Type Description Default
3 Data Input 3 UINT
This is a MODBUS address. The 3rd word in
PZD of cyclic output data will be sent to this
address if select Module = "4 PKW, 4 PZD".
0x0000
4 Data Input 4 UINT
This is a MODBUS address. The 4th word in
PZD of cyclic output data will be sent to this
address if select Module = "4 PKW, 4 PZD".
0x0000
5 Data Output 1 UINT
This is a MODBUS address. PD-01 will
monitor this address, and copy the return
data to the 1st word in PZD of cyclic input
data.
0x2101
6 Data Output 2 UINT
This is a MODBUS address. PD-01 will
monitor this address, and copy the return
data to the 2nd word in PZD of cyclic input
data.
0x2102
7 Data Output 3 UINT
This is a MODBUS address. PD-01 will
monitor this address, and copy the return
data to the 3rd word in PZD of cyclic input
data if select Module = "4 PKW, 4 PZD".
0x2103
8 Data Output 4 UINT
This is a MODBUS address. PD-01 will
monitor this address, and copy the return
data to the 4th word in PZD of cyclic input
data if select Module = "4 PKW, 4 PZD".
0x2104
9 d_state UINT
This is a flag. If address in Data Output 1 ~
Data Output 4 is continuous, set it to 1, and
set the others to 0.
0x0001
10 din_len UINT
This is a length, and unit is word. It specifies
the length of PD-01 to process data in PZD, if
user select the Module = "4 PKW, 4 PZD", but
din_len is 3, PD-01 will process 3 word and
ignore the 4th word.
0x0002
11 dout_len UINT
This is a length, and unit is word. It specifies
the length of PD-01 to monitor data from AC
Drive, if user select Module = "4 PKW, 4
PZD", but dout_len is 3, PD-01 will monitor 3
word and ignore the 4th address.
0x0002
12 LossDPComTreat UINT
This variable indicates that the PD-01 will
take action when communication with
Profibus network is lost, the value can be
assigned as follows:
00 – Ignore event and continue;
01 – Stop according to Pr “Stop Method” in
VFD series Drives.
0x0001