Setup and Operation
81331 Rev 01 Nov 2010
21
Figure 7: Typical Test Setup for Transformer Excitation Current Measurements
1. Locate the test set at least 6 ft (1.8 m) from the specimen to be tested.
2. Connect the test ground to a low impedance earth ground on the
specimen (if possible). This should always be the first cable connected
and last removed
3. Connect the control and power cables between the control and HV units.
Make sure that the bayonet type plugs are fully locked on the receptacles.
4. Connect the measurement cable with the red colored boot to the INPUT
RED receptacle. Make sure the connector locks to the receptacle. If
required, connect the measurement cable with the blue colored boot to
the INPUT BLUE receptacle.
5. Connect the external interlock cables or a test area interlock system to
the INTERLOCK 1 and 2 receptacles. Make sure the plugs are fully
seated and locked on the receptacles.
DELTA4000
CONTROL UNIT
DELTA4000
HIGH
VOLTAGE
UNIT