Delta 4000 Instruction Manual Page 37

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 36
Delta Control User Interface
81331 Rev 01 Nov 2010
29
Frequency and Temperature
This is where you specify at which test frequency you want to perform the test.
This is in most cases the same as the network frequency (but if you would like to
test at e.g. 55 Hz you simply enter 55). Note that “Line Frequency” in the setting
tab must be set to actual line frequency, 50Hz or 60 Hz.
Insulation properties are temperature dependent and the test object temperature
is a very important parameter. The average temperature of the test object
insulation should be entered.
These two parameters need to be set in order to start a measurement.
Test Type
Select which Test you want to perform. In the setting tab you set your preference
for tan delta or power factor readings.
The available tests are:
Power Factor/Tan-
Delta
Power Factor or Tan-Delta test is a semi
automatic test sequence performed at a preset
v
oltage and line frequency. The system will
ramp up the voltage to the set voltage and
measure the Power Factor or Tan-Delta and
after the completed test, ramp voltage down
and stop the test and present the result.
Excitation Current
A
n excitation current is a standard test that is
helpful in determining winding or core
problems in transformers.
Page view 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 107 108

Comments to this Manuals

No comments