Delta 4310 User Interface
81331 Rev 01 Nov 2010
49
Intelligent Temperature Correction, ITC
As a unique feature Delta4000 also offers ITC, Intelligent Temperature
Correction. With ITC the actual temperature correction for a certain
measurement object is estimated by measuring an additional frequency sweep
after performing the standard single frequency measurement. The information
from the sweep test is then used to estimate the correct temperature correction
from measurement temperature to 20°C reference (patent pending).
Note: Temperature range for ITC is 5-50° measurement/insulation
temperature. The frequency range for performing ITC should be 2-500
Hz. Selecting a higher low frequency will limit the temperature range.
Voltage Dependence Detection
Another unique feature in Delta 4000 is automatic Voltage Dependence
Detection (patent pending). In every test, Delta4000 measures the harmonic
content of the signal and based on this information it calculates a Voltage
Dependence Factor, VDF. If this value is too high (default > 0.05) the number
turns red, indicating a voltage dependence of the test object i.e. the dissipation
factor is pending the test voltage. In this situation a tip-up (step voltage) test
should be performed to verify and quantify the voltage dependence.