Description of Tets
Circuit Breaker Overall Tests
Prior to the overall insulation tests, remove the breaker from its cubicle or cell.
Tests may be performed either with or without arc chutes installed. This should
be noted in the Comments field for future reference.
The breaker will remain in the open position for all tests.
Tests 1 to 6 (C
1G
, C
2G
, C
3G
, C
4G
, C
5G
, C
6G
) - These are measurements of the
ground insulation of each pole of the breaker with the breaker in the open
position. Test 1 is indicated by Insulation Tested C
1G
, Test 2 by Insulation
Tested C
2G
, etc. The HV cable is connected to each pole, in turn, with all other
poles floating (no connection). The breaker frame must be connected to station
ground. Test mode is GST-GND.
Test 7 (C
12
) - This is a measurement of the insulation between the poles on
Phase 1 or Phase A, and is indicated by Insulation Tested C
12
. The HV cable is
attached to Pole 1 and the LV Red lead is attached to Pole 2. All other breaker
poles are left floating. This test is performed with the breaker open. Test mode
is UST-R.
Test 8 (C
34
) - This is a measurement of the insulation between the poles on
Phase 2 or Phase B, and is indicated by Insulation Tested C
34
. The HV cable is
attached to Pole 3 and the LV Red lead is attached to Pole 4. All other breaker
poles are left floating. This test is performed with the breaker open. Test mode
is UST-R.
Test 9 (C
56
) - This is a measurement of the insulation between the poles on
Phase 3 or Phase C, and is indicated by Insulation Tested C
56
. The HV cable is
attached to Pole 5 and the LV Red lead is attached to Pole 6. All other breaker
poles are left floating. This test is performed with the breaker open. Test mode
is UST-R.
Diagnostic Tests
These tests provide flexibility for performing more diagnostic tests in the event
that an area of concern presents itself. Each test line allows the operator to
choose between test modes UST-R and/or GST-GND. A detailed description of
the tests performed should be documented on the form, both in the
Specimen/Connection field and the form Comments field.
Page view 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 107 108

Comments to this Manuals

No comments