Delta 4310 User Interface
81331 Rev 01 Nov 2010
63
Tests 22 to 24 - These are tests of oil samples taken from each phase of the
breaker (either 1 or 3). Each sample of oil is tested separately in an accessory oil
test cell. Follow oil cell instructions for details on cell cleaning and filling.
Record the temperature of the oil sample in the Nameplate section at the top of
the form. Test mode is UST-R.
92520 - SF6 Dead Tank Circuit Breaker form
Basic Form Information
The PF SF6 Dead Tank Circuit Breaker form is used for power factor testing
medium and high voltage SF6 circuit breakers. These are typically found in
outdoor transmission and distribution substation applications. Dead tank circuit
breakers are those whose high voltage interrupting chamber is housed in an earth
grounded enclosure or tank.
SF6 dead tank circuit breakers occasionally utilize condenser bushings with test
taps which should be routinely tested whenever the overall insulation of the
breaker is tested. If so equipped, all bushing nameplate information should be
documented on the test form.
Test modes are mentioned in the description of tests below. However, the test
form is pre-programmed with the appropriate test modes to automatically be
performed.