Delta 4310 User Interface
81331 Rev 01 Nov 2010
75
Tests 28 to 36 are measurements of the arrester insulation. Only test voltage,
current and watts are recorded for arresters. The HV lead is attached to the
arrester HV terminal. No connection using the Red or Blue leads is necessary.
The Test Mode used is GST-GND. Once the HV lead is connected, right-click
on the blue highlighted field on the desired test line to initiate the test sequence.
Follow the onscreen instructions to complete the test.
Bushing Hot Collar Tests
Hot collar tests are generally performed on HV bushings that do not have test
taps. However, these tests may also be done as an additional test if the bushings
have test taps
Tests 37 to 46 - These tests measure the outer shell insulation of the bushings,
including surface leakage and leakage current from the bushing surface through
the insulating material to the center conductor. A conductive strap is placed
around the bushing, below one of the skirts, normally the top skirt, and
connected to the HV lead. The Red lead is connected to the bushing conductor.
Test mode GST-GND is automatically programmed by the test form.
Multiple hot collar tests can be performed on each bushing. For each test, the
location of the strap should be clearly indicated on the form in the Designation
column.