81331 Rev 01 Nov 2010
1
1
Introduction
Receiving Instructions
Check the equipment received against the packing list to ensure that all materials
are present. Notify Megger of any shortage.
Examine the instrument for damage received in transit. If damage is discovered,
file a claim with the carrier at once and notify Megger, giving a detailed
description of the damage.
This instrument has been thoroughly tested and inspected to meet rigid
specifications before being shipped. It is ready for use when set up as indicated
in this manual.
General Information
The DELTA4000 is used for shop and field testing of high-voltage electrical
insulating systems at test voltages up to 12 kV. Test results can be used to
evaluate the nature and quality of electrical insulating materials and
manufacturing processes to reveal contamination, fractures, punctures, and other
defects that accompany the aging of insulation. The test set comprises of a
control unit, a high-voltage unit, cables, and canvas carrying bags. Refer to the
Specifications section for a list of included accessories.
Tests are made by measuring the capacitance and dissipation factor (power
factor) of a specimen. The values measured will change when undesirable
conditions exist, such as moisture on or in the insulation; presence of conductive
contaminants in insulating oil, gas or solids; presence of internal partial
discharges etc.
The test set measures insulation properties in high-voltage power equipment
such as transformers, bushings, rotating machines, cables, circuit breakers,
capacitors, surge (lightning) arresters etc. In addition the test set can also measure
transformer excitation current and transformer turns ratio (with optional TTR
capacitor).
Delta4000 makes all standard Ungrounded Specimen Tests (UST) and Grounded
Specimen Tests (GST) on high-voltage apparatus and key features include: