Turns Ratio Tests
Measurements of transformer winding ratio can be made with a high voltage
power factor test set when a TTR capacitor is available. Depending on the
voltage rating of the winding being energized, tests can be made up to 10kV.
The significance of this is that higher volts per turn can be applied to the
winding, stressing the winding turn-to-turn insulation more than low voltage
ratio test sets. This may be able to detect high resistance turn faults that may be
undetectable at lower voltage. The tests are performed one phase at a time on
three-phase transformers.
To enable this portion of the test form, select the Show TTR Tests checkbox at
the top of Page 1. A table for ratio test results will become visible near the end
of the form. You should select the Number of Tests based on how many
transformer taps you intend to test.
The first test must measure the capacitance of the Standard Capacitor, in pico-
Farads (pF).
Connect the test set leads, the HV lead and the Red measurement lead,
directly to the capacitor.
Initiate the test by right clicking on the blue field for the Standard
Capacitor.
Subsequent tests require the HV lead to be connected to one side of a HV
winding (e.g. H1/U/A) where the other side of the HV winding is grounded to
the tank (e.g. H0/N/N). The corresponding winding on LV side is grounded on
one side and on the other side is connected to Red lead via the capacitor.
By enter the winding voltage levels in the form, the assessment is automatic.
Exciting Current Tests
Measurements of the individual phase excitation current values are valuable in
determining defects in the transformer core and coils. Excitation current
measurements are generally performed on the high voltage winding only, to
minimize the amount of current required.
NOTE: All bushing shorting leads must be removed for exciting current
measurements. If the low voltage winding has a neutral, connect the
neutral bushing as it normally is in-service (grounded or ungrounded).
Measurements are usually made one phase at a time. Connections should be
documented in the fields provided at the top of the table. For initial or
commissioning tests, perform the measurements on each possible primary and