Delta Digital timer User Manual Page 53

  • Download
  • Add to my manuals
  • Print
  • Page
    / 74
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 52
Cat. No.
Parameters
MOUNTING DIMENSION (mm)
CONNECTION DIAGRAM
ORDERING INFORMATION
MD71B9
MD71BH MD71BF
MD71B9
MD71BH
MD71BF
UV / OV with adjustable 0 to 15 m on delay time, 1C/O
UV / OV with adjustable 0 to 15 s on delay time, 1C/O
UV / OV with adjustable 0 to 15 s off delay time, 1C/O
Cat. No.
Description
60.0
P
UV/OV
RELAY
P
UV/OV
RELAY
3 Phase 4 Wire, 240 VAC
1 Phase - 240 VAC
Frequency
Power Consumption (Max.)
48 - 63 Hz
5 VA
Time Delays:
ON Delay
LED Indication
Operating Temperature
Storage Temperature
Enclosure
Dimension (W x H x D)
Weight
(in mm)
(unpacked)
Mounting
Certification
Trip Levels: Under Voltage
Over Voltage
OFF Delay
Setting Accuracy
55% - 95%
105% - 125%
Setting Accuracy: 5 % of full scale ±
Note: Voltage setting is with respect to neutral
0 to 15 m (Adjustable)
5 s (Fixed)
0 to 15 s (
5 s (Fixed)
Adjustable) 5 s (Fixed)
0 to 15 s (Adjustable)
± 10 % of full scale
1 C/O
5A (Resistive) @ 250 VAC / 28 VDC
5
1 x 10
6
3 x 10
(SPDT)
Separate indications for Power ON, UV and OV
O
-10 C To + 55 C
O O
-25 C To + 70 C
O
Flame Retardant UL 94V0
36 X 90 X 60
120 g
Base / DIN rail
Relay Output
Contact Rating
Electrical Life
Mechanical Life
EMI/ EMC
Radio Interference Suppression
ESD
Electrical Fast Transients
Surges
Voltage Dips, Interruptions
Isolation
Degree of Protection
IP 20 for Terminals, IP 40 for Enclosure
Utilization Category
AC - 15
DC - 13
• Protects against Phase Loss,
Phase Reversal and Phase-Phase Unbalance
• Can be configured for 3 phase 4 wire or 1 phase system
• Selectable Over/Under voltage trip level
Adjustable time delay
• LED indications for power and fault conditions
Supply Monitoring Series SM 500
Note: 1) In the event of Phase sequence or phase loss, OFF delay is 100 ms
• Voltage sensing principle
• 1 C/O or 2 C/O configuration
51
Supply Voltage ( )
CISPR 14-1
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-11
Test voltage between input & output - IEC 60255-5, 2kV
Ed. 5.0 (2005-11) Class B
Ed. 1.2 (2001-04) Level II
Ed. 2.0 (2004-07) Level IV
Ed. 2.0 (2005-11) Level IV
Ed. 2.0 (2004-03) All 7 Levels (AC), IEC 61000-4-29 Ed. 1.0 (2000-08) All 5 Levels (DC)
Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/ 1.5 A
Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A
(of )
(of )
RoHS
Compliant
Page view 52