Delta Digital timer User Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 74
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
Cat. No.
Parameters
MOUNTING DIMENSION (mm)
ORDERING INFORMATION
MG73B9
MG73BH MG73BF
CONNECTION DIAGRAM
P
P
Cat. No.
Description
MG73BH
MG73BF
MG73B9
3 Phase 4 Wire, UV/OV & single phasing Protection with adjustable 0 to 15 s On delay time, 2 C/O
3 Phase 4 Wire, UV/OV & single phasing Protection with adjustable 0 to 15 s Off delay time, 2 C/O
3 Phase 4 Wire, UV/OV & single phasing Protection with adjustable On delay , 2 C/O0 to 15 m time
Frequency
Power Consumption (Max.)
3 Phase 4 Wire, 240 VAC
1 Phase, 240 VAC
48 - 63 Hz
5VA
55% - 95%
105% - 125%
10%
Yes
7 V of trip voltage (factory set) Note: Voltage setting is with respect to neutral ± 2 V
Certification
o
- 10 to +55 C
o
- 25 to +70 C
o
C
o
C
UL 94VO
36 X 90 X 60
120 g
Base / DIN rail
Mounting
Operating Temperature
Storage Temperature
Enclosure
Dimension (W x H x D)
Weight
(in mm)
(unpacked)
Degree of Protection
LED Indication
Separate indications for Power ON, UV, OV; ON: Phase Reverse, BLINK: Phase Unbalance (Asy.)
Trip Settings :
Under Voltage
Over Voltage
Phase - Phase Unbalance (Asy.)
Phase Reverse Detect
Hysteresis
Setting Accuracy
± 10 % of full scale.
Relay Output
Contact Rating
Electrical Life
Mechanical Life
2 C/O (DPDT)
5A (Resistive) @ 250 VAC / 28 VDC
5
1X10
Time Delays:
ON Delay
OFF Delay
0 to 15 m (Adjustable)
5 s (Fixed).
0 to 15 s (Adjustable)
5 s (Fixed)
5 s (Fixed)
0 to 15 s (Adjustable)
6
3X10
IP 20 for Terminals, IP 40 for Enclosure
EMI/ EMC
Radio Interference Suppression
ESD
Electrical Fast Transients
Surges
Voltage Dips, Interruptions
Isolation
Utilization Category
AC - 15
DC - 13
Note: 1) In the event of Phase sequence or phase loss, OFF delay is 100 ms
Supply Monitoring Series SM 500
52
Supply Voltage ( )
Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/ 1.5 A
Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A
CISPR 14-1
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-11
Test voltage between input & output - IEC 60255-5, 2kV
Ed. 5.0 (2005-11) Class B
Ed. 1.2 (2001-04) Level II
Ed. 2.0 (2004-07) Level IV
Ed. 2.0 (2005-11) Level IV
Ed. 2.0 (2004-03) All 7 Levels (AC), IEC 61000-4-29 Ed. 1.0 (2000-08) All 5 Levels (DC)
(of )
(of )
RoHS
Compliant
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 73 74