53
Cat. No.
Parameters
Supply Monitoring Series SM 501
MOUNTING DIMENSION (mm)
CONNECTION DIAGRAM
ORDERING INFORMATION
MG53BH
MG53BF MG53BI
L1 L2 L3
SM 501
15
16 18
25
2826
BYR
THREE PHASE APPLICATIONS
Description
415 VAC, adjustable On & fixed Off Delay time, 2 C/O
415 VAC, adjustable Off & fixed On Delay time, 2 C/O
415 VAC, 94 volt asymmetry, with fixed Off & On Delay time, 2 C/O
415 VAC, Under/Over Voltage, with fixed 3 m / Off Delay time, 2 C/O
220 VAC, adjustable 2 C/O
220 VAC, adjustable Off & fixed On Delay time, 2 C/O
0.5 - 15 s 5 s
0.5 - 15 s 5 s
fixed 5 s
On 5 s
0.5 - 15 s On & 5 s fixed Off Delay time,
0.5 - 15 s 5 s
Cat. No.
MG53BH
MG53BF
MG53BI
MG53BO
MG63BH
MG63BF
415 VAC
10 VA
± 10 % of full scale
Frequency
Power Consumption (Max.)
Time Delays
ON Delay
OFF Delay
Setting Accuracy
0.5 -15 s (adjustable)
5 s (fixed)
5 s (fixed)
0.5 - 15 s (adjustable)
5 s (fixed)
5 s (fixed)
± 10 % of full scale ± 10 % of full scale
48 - 63 Hz
55% - 95%
105% - 125%
Yes
7 V of trip voltage± 2V
Trip Settings :
Under Voltage
Over Voltage
Phase Reverse Detect
Phase - Phase Unbalance
Hysteresis
10%
94 V
UL 94V0
36 X 90 X 60
120 g
Base / DIN rail
Contact Rating
Electrical Life
Enclosure
Dimension (W x H x D)
Weight
(in mm)
(unpacked)
Mounting
Degree of Protection
Certification
5A (Resistive) @ 250 VAC / 28 VDC
5
1 x 10
Relay Output
2 C/O (DPDT)
Mechanical Life
6
3 x 10
IP 20 for Terminals, IP 40 for Enclosure
EMI/ EMC
Radio Interference Suppression
ESD
Electrical Fast Transients
Surges
Voltage Dips, Interruptions
Isolation
o o
- 10 C to +55 C
o o
- 25 C to +70 C
Operating Temperature
Storage Temperature
LED Indications
Separate indications for Power ON: UV, OV, ON: Phase Reverse, BLINK: Phase Unbalance
Utilization Category
AC - 15
DC - 13
Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3/1.5 A
Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A
• Protects against Phase Loss,
Phase Reversal and Phase-Phase Unbalance
• Suitable for 3 phase 3 wire systems
• Selectable Over/Under voltage trip level
Adjustable time delay
• Model for selectable Phase Asymmetry
• LED indications for power and fault conditions
• Voltage sensing principle
• 2 C/O configuration
TERMINAL TORQUE & CAPACITY
Torque 0.54 N.m (5 Lb. in)
Terminal Screw - M 2.5
2
1 x 0.2 - 3.3 mm Solid Wire /
single wire ferrule
2 x 0.2 - 1 mm Insulated with
twin ferrule
2
3.5 mm
AWG 1 x 24 to 12
Note: 1) In the event of Phase sequence or phase loss, OFF delay is 100 ms
Supply Voltage ( )
CISPR 14-1
IEC 61000-4-2
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-11
Test voltage between input & output - IEC 60255-5, 2kV
Ed. 5.0 (2005-11) Class B
Ed. 1.2 (2001-04) Level II
Ed. 2.0 (2004-07) Level IV
Ed. 2.0 (2005-11) Level IV
Ed. 2.0 (2004-03) All 7 Levels (AC), IEC 61000-4-29 Ed. 1.0 (2000-08) All 5 Levels (DC)
(of )
(of )
RoHS
Compliant