17G715GF2
17G715KF2
17G745GF2
17G745KF2
110-240V AC, Current Range 30 mA - 30 mA, 1 C/O + 1 NO, Manual Reset
110-240V AC, Current Range
220-415V AC, Current Range
220-415V AC, Current Range
30 mA - 30 mA, 1 C/O + 1 NO, Auto Reset
30 mA - 30 mA, 1 C/O + 1 NO, Manual Reset
30 mA - 30 mA, 1 C/O + 1 NO, Auto Reset
• Monitors, detects and protects power systems from earth leakage faults
• Wide range of selectable Earth Leakage Current: 30 mA - 30 A
• Configurable Earth Leakage Trip time: 0 - 10 s
• Wide auxiliary supply range: 110 - 240 VAC, 220 - 415 VAC
• Instantaneous trip for 5 times of set value of leakage current
• Test feature to check complete product functionality
• LED indication for relay status, CT open,
earth leakage fault & test/reset switch short
• Manual / Remote reset feature
• 1 C/O + 1 NO relay output
Cat. No.
Parameters
Power Consumption (Max.)
Overall Leakage Current ( I n)
220 - 415 VAC
50/60Hz
17G715GF2 17G745GF2
110 - 240 VAC
-20 to +20%
10 VA 5 VA
30 mA to 30 A (In 10 steps)
Green LED (ON)
Power
Leakage Current / TST
EL / CT
Red LED (ON) Relay Trip / (Blinking) CT OpenRed LED
By Bar Graph: 30% (Green), 45% (Green), 60% (Yellow), 75% (Red), Blink Test / Reset Switch is pressed
LED
Indication
ORDERING INFORMATION
Description
Cat. No.
17G715KF2 17G745KF2
Earth Leakage Relay Series CMR
65
Supply Voltage ( )
Supply Variation
Frequency
Utilization Category
AC - 15
DC - 13
Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/ 1.5 A
Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2/0.22/0.1 A
Reset
No. of Resets
4
Clear Auto Reset After 1 hour of healthy condition or supply interruption
Test / Reset
Local & Remote (Non Potential free contacts, upto 10 m)
Trip Time ( t in sec)
0.03 - 0.06 - 0.15 - 0.25 - 0.5 - 0.8 - 1 - 2.5 - 5 - 10
Threshold I n (A)
0.03 - 0.1 - 0.3 - 0.5 - 1 - 3 - 5 - 10 - 20 - 30
Type Class
CBCT
'A' True RMS measurement (As per IEC 60947-2 appendix M)
Max. Crest Factor
5 (for 30 mA to 30 A)
Reset Enable Below 50% on current threshold set by potentiometer & in presence of CBCT
Reset Time
< 1s
Manual Reset Manual ResetAuto Reset Auto Reset
-20% (Including CBCT Accuracy)
Accuracy
+/- 2%
Storage Temperature
Operating Temperature
Humidity (Non Condensing)
-20 to + 80°C°C
-15 to + 60°C°C
95% (Rh)
Degree of Protection
Mounting
No. of Turns
CBCT 3
CBCT 2
CBCT 1
Dimensions in mm
without enclosure
ID X OD X H
45 X 65 X 15
65 X 90 X 15
100 X 125 X 15
1500
Base / DIN Rail
IP 20 for Terminals, IP 40 for Enclosure
EMI/ EMC
Certification
Setting Accuracy
Repeat Accuracy
RoHS
Compliant
Harmonic Current Emissions
ESD
Radiated Susceptibility
Electrical Fast Transients
Surges
Conducted Susceptibility
Voltage Dips & Interruptions
Conducted Emission
Radiated Emission
IEC 61000-3-2
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-11
CISPR 14-1
CISPR 14-1
Ed. 3.0 (2005-11) Class A
Ed. 1.2 (2001-04) Level II
Ed. 3.0 (2006-02) Level III
Ed. 2.0 (2004-07) Level IV
Ed. 2.0 (2005-11) Level IV
Ed. 2,2 (2006-05) Level III
Ed. 2.0 (2004-03) Level I, II, III, IV & V Class A, Level VI Class B
Ed. 5.0 (2005-11) Class A
Ed. 5.0 (2005-11) Class A
Enclosure
Dimension (W x H x D) (in mm)
Weight (unpacked)
Flame Retardant UL94-V0
18 X 60 X 85
70 g
1C/O (SPDT) + 1 NO (SPST)
5 A (Resistive) @ 240 VAC / 30 VDC
Ag Alloy
5
1X10
7
1X10
Relay Output
Contact Rating
Contact Material
Electrical Life
Mechanical Life
Environmental
Cold Heat
Dry Heat
Vibration
Repetitive Shock
Non-repetitive shock
IEC 60068-2-1 Ed. 6.0 (2007-03)
IEC 60068-2-2 Ed. 5.0 (2007-07)
IEC 60068-2-6 Ed. 7.0 (2007-12) 5g
IEC 60068-2-27 Ed. 4.0 (2008-02) 40g, 6ms
IEC 60068-2-27 Ed. 4.0 (2008-02) 30g, 15ms