PROFIBUS DP Slave Communicaion Module RTU-PD01
DVP-PLC Operation Manual
15
z Configuration method for DVP04PT-S
Refer to the figure below for the relevant parameters to configure DVP04PT-S.
Definitions of configuration items:
Parameter Value Definition
Location 0 ~ 7
The location of DVP04PT-S at the right side of RTU-PD01. The
location of the first special I/O module at the right side of
RTU-PD01 is 0, the second is 1 and so forth. This rule is only
applicable on special I/O modules.
Centigrade (°C)
Collecting temperature in Centigrade by CH1 ~ CH4 on
DVP04PT-S
Temperature mode
Fahrenheit (°F)
Collecting temperature in Fahrenheit by CH1 ~ CH4 on
DVP04PT-S
Current value
Current value of the collected temperature at CH1 ~ CH4 on
DVP04PT-S
Input value mode
Average value
Average value of the collected temperatures at CH1 ~ CH4 on
DVP04PT-S
Average times 1 ~ 4096 The average times.
z Configuration method for DVP04TC-S
Refer to the figure below for the relevant parameters to configure DVP04TC-S.