PROFIBUS DP Slave Communicaion Module RTU-PD01
DVP-PLC Operation Manual
25
10 Application Example 1
Mission:
Exchanging data between S7-300 (Siemens PLC) and RTU-PD01 through PROFIBUS DP network
Connecting RTU-PD01 to PROFIBUS DP network:
1. S7-300 as the PROFIBUS DP master; RTU-PD01 as the slave. See the PROFIBUS DP network in
the figure below.
2. Set the PROFIBUS address of RTU-PD01 to “1”.
3. Connect RTU-PD01 to DVP16SP, DVP08SP, DVP04AD-S and DVP02DA-S in order at its right hand
side. Make sure the connection and wiring between RTU-PD01 and the special I/O modules and to
the entire network is correct.
Configuring RTU-PD01 in PROFIBUS DP network (the software configuration):
z Create a new project by software wizard
1. Open SIMATIC Manager.