PROFIBUS DP Slave Communicaion Module RTU-PD01
DVP-PLC Operation Manual
4
Serial transmission
speed supported
(auto-detection)
9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;
12Mbps (bits per second)
Electrical Specification
Power supply voltage 24VDC
Insulation voltage 500VDC
Power consumption 2.5W
Weight 90g
Environment
Noise immunity
ESD (IEC 61131-2,IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2,IEC 61000-4-4): Power Line:±2kV,Digital Input:±2kV
Comunication I/O: ±2kV
Conducted Susceptibility Test (EN61000-4-6, IEC 61131-2 9.10): 150kHz ~
80MHz,10V/m
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Storage/operation
Operation: 0°C ~ 50°C (temperature), 50 ~ 90% (humidity), pollution degree 2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Shock/vibration
immunity
International standards: IEC 61131-2,IEC 68-2-6 (TEST Fc)/IEC 61131-2& IEC
68-2-27 (TEST Ea)
3 Installation
3.1 Definition of PROFIBUS DP Port
PIN PIN name Definition
1 -- N/C
2 -- N/C
3 RxD/TxD-P Sending/receiving data P(B)
4 -- N/C
5 DGND Data reference potential (C)
6 VP Power voltage – positive
7 -- N/C
8 RxD/TxD-N Sending/receiving data N(A)
9 -- N/C
1
5
9
6
3.2 Connecting to PROFIBUS DP Port
Insert PROFIBUS DP bus connector into PROFIBUS DP port on RTU-PD01 (see the figure below)
Screw it tight to ensure RTU-PD01 and PROFIBUS DP bus are properly connected.