PROFIBUS DP Slave Communicaion Module RTU-PD01
DVP-PLC Operation Manual
6
4 Components
4.1 RUN/STOP Switch
Status Description
1. Special I/O module switches from RUN to STOP.
2. All Y points on digital output module turn OFF.
3. Modbus function switch
RUN => STOP
4. RUN LED turns off.
1. RTU-PD01 re-detects the number of digital I/O points and
specialI/O modules.
2. Special I/O module switches from STOP to RUN.
3. Enable digital I/O modules.
4. Enable Modbus function.
STOP
RUN
STOP => RUN
5. RUN LED turns on.
4.2 Address Setup Switch
The two rotary address setup switches, x16
0
and x16
1
, set up the node address of RTU-PD01 on
PROFIBUS DP network in hex form. The range for rotation is 0 ~ F.
Address Definition
H’1~ H’7D Valid PROFIBUS address
H’0 or H’7E ~ H’FF
Invalid PROFIBUS address. NET LED will flash in red
color if the node address falls within this range.
0
x16
1
x16
Example: If you need to set the node address of RTU-PD01 to 26 (decimal), simply switch x16
1
switch
to “1” and x16
0
to “A”. 26 (decimal) = 1A (hex) = 1x16
1
+ Ax16
0
.
Note:
z Switch off the power supply before setting up the node address of RTU-PD01. Re-power the
module after the setup is completed.
z Changing the value on the switch during the operation of RTU-PD01 is invalid.
z Use slot type screwdriver to set up the switch. Be careful not to scratch the module.