5.2 AC Grid Connection: L + N + PE
WARNING! Death and serious injuries may occur.
Before AC wiring, please ensure AC breaker is switched off.
For RPI-H5, users must aware that AC configuration Setting must be set
correctly otherwise this device can not work. There are two types of AC
configurations (shown in figure 5-2) that are used in electricity systems. For
“AC Configurat.” setting please see chapter 7.2.2
Star configuration (3 phases + Neutral): L–N
(default), The voltage between each phase
and the neutral is 230/220 V. The voltage
between two phases is 400/380V.
Delta configuration (3 phased wires only) : L–L,
The voltage between two phases are
230/220V. As there is no neutral, there is no
phase-neutral voltage.
Figure 5-2 AC configurations
5.2.1 Required protective devices and cable cross-sections
Recommended upstream protection
Power rating Upstream circuit breaker
3.75kVA(RPI-H3), 6.25 kVA(RPI-H5)
20A(RPI-H3), 30A(RPI-H5)
Please use proper wire to connect correct poles (According to the Table 5-1).
Table 5-1 AC wire requirement
Current Rating Wire size Torque
>20A (RPI-H3), >30 A (RPI-H5)
3-4mm
2
/ 12 AWG 0.8~1Nm
!