Delta RPI-H3 Service Manual Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
21
Power vs. frequency curve for VDE-AR-N 4105
Power vs. frequency curve for CEI-021
Figure 6-1 Power vs. frequency characteristic
6.2
Reactive Power Control
With active power output, it must be possible to operate the generating plant in
any operating point with at least a reactive power output corresponding to a
active factor at the network connection point of
cos ϕ = 0.8 underexcited to 0.8 overexcited
(VDE-AR-N 4105,CEI 0-21 cos ϕ = 0.9 underexcited to 0.9 overexcited)
Values deviating from the above must be agreed upon by contract. With active
power output, either a fixed target value for reactive power provision or a