Inconsistent
defective the inverter
A22: Internal
Comm Fault_R
1. Red. CPU is idling
2. The communication
connection is disconnected
1. Check reset and crystal in Red. CPU
2. Check the connection between Red. CPU
and DSP
A23: Internal
Comm Fault_D
1. DSP is idling
2. The communication
connection is disconnected
3. The communication circuit
malfunction
1. Check reset and crystal in DSP
2. Check the connection between DSP and
COMM
3. Check the communication circuit
A24: Residual
Curr Over
Rating
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground
3. Either side of boost driver or
boost choke malfunction
4. Detection circuit malfunction
1. Check the insulation of Solar inputs
2. Check the capacitance (+ <-> GND & -
<-> GND), must < 2.5uF. Install an external
transformer if necessary
3. Check boost driver & boost choke
4. Check the detection circuit inside the
inverter
A25: Ground
Fault
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground or both.
3. Detection circuit malfunction
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel if
necessary
3. Check the detection circuit inside the
inverter
A27: RCMU
Circuit Fail
1. RCMU is disconnected
2. Detection circuit malfunction
1. Check the RCMU connection inside the
inverter
2. Check the detection circuit inside the
inverter
A28: Relay
Short
1. One or more relays are
sticking
2. The driver circuit for the
relay malfunction
1. Replace the defective relay(s)
2. Check the driver circuit inside the inverter
A29: Relay
Open
1. One or more relays are
abnormal
2. The driver circuit for the
relay malfunction
3. The detection accuracy is
not correct for Vgrid and Vout
1. Replace the defective relay(s)
2. Check the driver circuit inside the inverter
3. Check the Vgrid and Vout voltage
detection accuracy
A30: Bus
Unbalance
1. Not totally independent or
parallel between inputs
2. PV Array short to Ground
1. Check the inputs connections
2. Check the PV Array insulation
3. Check the driver circuit for boost inside