33Operation and installation manual SOLIVIA 5.0 AP G3 TR
LED STATUS
DISPLAY
MESSAGE
CAUSE ELIMINATION
green: <off>
red: <off>
yellow: <on>
AC relay
failure
One of the anti-islanding
protection output relays is
faulty / defective.
The solar inverter is defective.
Return the device.
green: <ashes>
red: <off>
yellow: <off>
Calibration
ongoing
Check internal settings. Normal function before input mode.
green: <off>
red: <off>
yellow: <on>
DC injection
failure
DC component of input-
side alternating current is
too high.
If the fault persists after the device
has been reset, please inform your
service technician.
green: <off>
red: <off>
yellow: <on>
Error # 301
Internal communication
error or hardware fault.
If the fault persists after the device
has been reset, please inform your
service technician.
green: <off>
red: <off>
yellow: <on>
Error # 302
The device trips and
reverts to grid input mode
once the temperature has
dropped.
Check the installation site (no
direct sunlight, air circulation).
green: <off>
red: <on>
yellow: <off>
Error # 506
Error # 508
Isolation resistance fault
on the DC side during
start-up phase (# 508) or
running phase (# 506).
Check the isolation resistance on
the DC side of the PV modules.
green: <on>
red: <on>
yellow: <off>
Isolation
start-up
warning
Isolation run-
ning warning
Isolation resistance fault
on the DC side during
start-up phase or running
phase.
You must check the isolation
resistance on the DC side of the
PV modules. Solar inverter is still
feeding!
green: <on>
red: <on>
yellow: <off>
PV+ groun-
ding fault
PV- groun-
ding fault
Connection PV+ (PV-)
to GND is interrupted or
wrong pole is connected
to GND.
Check that the GND connection
has been made correctly and/or
check the fuse in the grounding
path. Change the fuse if necessary.
The solar inverter remains in feed-
in operation.
green: <off>
red: <off>
yellow: <on>
Revision
error
Versions of hard- and soft-
ware are not compatible.
If the fault persists after the device
has been reset, please inform your
service technician.
green: <on>
red: <on>
yellow: <on>
Self test
ongoing
Initialization of solar inver-
ter on start-up.
The rst time the solar inverter is
started up:
Normal function with a PV cell vol-
tage of between 100 V and 150 V.
green: <ashes>
red: <off>
yellow: <off>
PV power too
low
Insufcient input power.
Insufcient insolation (dawn/twi-
light).
Check the PV cell voltage via the
display in the N menu.
green: <ashes>
red: <off>
yellow: <off>
PV voltage
too low
PV generator voltage bet-
ween 100 V and 150 V.
Insufcient insolation.
Check the PV cell voltage via the
display in the N menu.
green: <ashes>
red: <off>
yellow: <off>
Synchronize
to AC
Checks grid voltage and
grid frequency for grid
input mode.
Normal function before input mode.