APPENDIX 1
The table below is based on Table 310.16 in the National Electric Code 2011 Edition
Allowable ampacitier of insulated condutors rated 0 through 2000 volts, 75
0
C through 90
0
C. Not more than
three current-carrying conductors in Raceway, Cable or Earth (Direct Buried). Adjusted for 40
0
C (104
0
F)
ambient temperature.
Copper Copper Aluminum Aluminum
Copper Clad Aluminum Copper Clad Aluminum
75
0
C90
0
C75
0
C90
0
C
Wire Type:
Wire Type: TBS,SA.
TBS,SA.SIS SIS, THHN
Wire Type: FEP,FEPB,MI,RHH Wire Type: THHW, THW-2
RHW RHW-2,THHN RHW THWN-2,RHH
THHW, THW THHW, THW-2 THHW, THW RHW-2, USE-2
THWN, XHHW XHH, XHHW SIZE AWG THWN, XHHW XHH, XHHW
USE,ZW XHHW-2, ZW-2 OR kcmil USE XHHW-2, ZW-2
44 50 8 35 41
57 68 6 44 55
75 86 4 57 68
88 100 3 66 77
101 118 2 79 91
114 137 1 88 105
132 155 1/0 106 123
154 177 2/0 119 137
176 205 3/0 136 159
202 237 4/0 158 187
224 264 250 180 209
251 291 300 202 232
273 319 350 220 255
295 346 400 238 278
334 391 500 273 319
370 432 600 299 350
405 473 700 330 382
418 487 750 339 396
431 505 800 348 410
458 532 900 374 437
480 560 1000 392 455
519 605 1250 427 496
550 642 1500 458 532
572 669 1750 480 560
585 683 2000 493 573
For addition information see table 310.16 of the National Electric Code