ProCon MCS
670 Hidro
740 Hidro
800 Hidro
850 Hidro
Nominal Heating Capacity
kW
25-630
20-700
25-750
30-800
Nominal Thermal Power (80/6C)
kW
24.45-617.5
19.52-686.2
24.45-735.5
29.39-784.9
Nominal Thermal Power (50/3C)
kW
26.63-671
21.3-745.5
26.63-798.8
31.95-852
Thermal Efficiency at Max Output (80/60°C)
%
98.02
98.03
98.06
98.11
Thermal Efficiency at 30% Output (50/30°C)
%
105.3
105.3
105.3
105.3
Thermal Efficiency at Max Output (50/30°C)
%
106.5
106.5
106.5
106.51
NOx Class
5
5
5
5
Gas Consumption G20
m
3
/h
2.65-66.67
2.12-74.07
2.65-79.37
3.17-84.66
Gas Consumption G30
Kg/h
1.97-49.69
1.58-55.2
1.97-59.15
2.37-63.09
Gas Consumption G31
Kg/h
1.94-48.94
1.55-54.38
1.94-58.26
2.33-62.15
Min/Max Working Pressure
Bar
1/6
1/6
1/6
1/6
Number of Burners
#
4
4
4
4
Water Content of Individual Heat X
L
65
77
81
85
Water Content of Unit
L
142.3
154.4
159.4
164.5
Equipment Type
B23
B23
B23
B23
Power Supply/Power
230V/3400
230V/3400
230V/3500
230V/3750
Empty Weight
Kg
1032
104
1075
1085
Dimension WxDxH
Mm
1550x1150x1552
1550x1150x1552
1550x1150x1552
1550x1150x1552
Flue Gas Mass Flow
Kg/h
42.1-1062
33.7-1180.1
42.1-1264.3
50.6-1348.6
Residual Flue Pressure
Pa
100
100
100
100
Carbon Dioxide Concentration
%
9.0
9.0
9.0
9.0
ProCon MCS
940 Hidro
1000 Hidro
1250 Hidro
1320 Hidro
Nominal Heating Capacity
kW
38-880
50-1000
25-1200
25-1250
Nominal Thermal Power (80/6C)
kW
37.3-864
49.1-982
19.52-1177.2
24.45-12226.5
Nominal Thermal Power (50/3C)
kW
40.47-937.2
53.25-1065
21.3-1278
26.63-1331.3
Thermal Efficiency at Max Output (80/60°C)
%
98.11
98.20
98.10
98.12
Thermal Efficiency at 30% Output (50/30°C)
%
105.3
105.3
105.3
105.3
Thermal Efficiency at Max Output (50/30°C)
%
106.5
106.5
106.5
106.5
NOx Class
5
5
5
5
Gas Consumption G20
m
3
/h
4.02-93.12
5.29-105.82
2.12-126.98
2.65-132.28
Gas Consumption G30
Kg/h
3-69.4
3.94-78.86
1.58-94.63
1.97-98.58
Gas Consumption G31
Kg/h
2.98-68.36
3.88-77.68
1.55-93.22
1.94-97.1
Min/Max Working Pressure
Bar
1/6
1/6
1/6
1/6
Number of Burners
#
4
4
4
4
Water Content of Individual Heat X
L
94
110
132
136
Water Content of Unit
L
174.5
191.6
250.2
255.2
Equipment Type
B23
B23
B23
B23
Power Supply/Power
230V/3900
230V/4000
230V/5400
230V/5500
Empty Weight
Kg
1117
1160
1624
1655
Dimension WxDxH
Mm
1550x1150x1552
1550x1150x1552
1550x1150x1552
1550x1150x1552
Flue Gas Mass Flow
Kg/h
64.1-1483.5
84.3-1685.8
33.7-2023
42.1-2107.2
Residual Flue Pressure
Pa
100
100
100
100
Carbon Dioxide Concentration
%
9.0
9.0
9.0
9.0