Appliance Fault Codes
The display will read as _:__. The first digit identifies the boiler module at fault.
The figures after the : are the fault codes detailed below.
Intervention of the water safety
thermostat
The burner turns off and the circulating pump operates at maximum
speed. The lock-out disappears and the regulator resets when the
temperature detected by the water safety thermostat falls below the
temperature limit
The ionization electrode does not detect a
flame
The flame control board goes into lock-out
The ionization electrode does not detect
the flame during operation of the burner
Maximum delivery temperature exceeded
The burner turns off and the circulating pump remains in operation
The ignition of the burner is impeded
The ionization electrode has detected a
flame before the burner has turned on
The ignition of the burner is impeded
The delivery temperature sensor is
interrupted or not working
The return temperature sensor is
interrupted or not working
Protection for reaching the maximum
Delta T permitted between delivery and
return temperatures.
The burner turns off and the circulating pump remains in operation
The circulating pump operates for 5 minutes at maximum speed to
withdraw heat from the system
The ionization electrode detects the flame
after the burner has turned off
The ignition of the burner is impeded
The combustion fan has broken and the
Non Return valve has locked open
The ignition of the burner is impeded
Electric fan speed out of control
The ignition is repeated when the fan speed is equal to +/-10% of that
required or it attempts to start immediately by pressing the reset button
The fume safety thermostat has been
interrupted
The burner turns off. The burner is reactivated using the RESET button
after the temperature of the flue has fallen below the limit
Combustion fan does not stop
The ignition of the burner is impeded
The condensate syphon/drain is blocked
The ignition of the burner is impeded
The service settings are disturbed by
electromagnetic interference
The ignition of the burner is impeded
The ignition of the burner is impeded
The power supply is lower than 190Vac
The burner ignition procedure waits until the supply voltage is greater
than 200Vac
The factory settings are disturbed by
electromagnetic interference
The ignition of the burner is impeded
An insufficient circulation of water has
been detected after 10 seconds of start up
Presence of air in the circulating pump
The circulating pump is blocked
Circulating pump and burner turn off
Circulating pump wiring defective
Communication interrupted with one or
more thermal modules
The ignition of the burner is impeded. The error received from the
cascade eBus is not detected by the local eBus: this action leads to the
blocking of the entire cascade
Communication interrupted with one or
more thermal module burners
The ignition of the burner is impeded. The error received from the local
eBus is not detected by the local eBus: this action leads to the blocking of
the entire cascade