Converting The Appliance To Burn LPG (G31)
Unless specified at the time of ordering the appliance/s will be supplied ready to operate on a Natural Gas
(G20) fuel supply.
The appliances data badge will indicate the type of fuel gas the modules have been set to operate with.
If the appliance is required to operate on LPG the following controller adjustments must be undertaken.
Boiler Type
Module
Range
Fuel
Injector
CO
2
% @
Max Output
Fan Speed @
Max Output
CO
2
% @ Min
Output
Fan Speed @
Min Output
MCS 210
10-100kW
Nat Gas G20
None
9.10
5600
8.90
1700
MCS 210
10-100kW
Propane G31
None
8.70
5600
8.55
1700
MCS 260
25-125kW
Nat Gas G20
None
9.10
6600
8.90
1800
MCS 260
25-125kW
Propane G31
None
8.70
6300
8.55
1800
MCS 320
30-150kW
Nat Gas G20
None
9.10
5400
8.90
1500
MCS 320
30-150kW
Propane G31
None
8.70
5200
8.55
1500
MCS 400
38-190kW
Nat Gas G20
None
9.10
5500
8.90
1500
MCS 400
38-190kW
Propane G31
None
8.70
5100
8.55
1500
MCS 535
50-249.5kW
Nat Gas G20
None
9.10
5850
8.90
1667
MCS 535
50-249.5kW
Propane G31
None
8.70
5535
8.55
1535
No mechanical restrictor / injectors are required.
Please refer to the controller adjustment section to make the necessary alteration to the fan speeds.