MCS 210 & 260 Valve Adjustment
Legend
1. Gas Valve Assembly
2. High Fire Adjuster (Gate Type) (Make small adjustments only)
3. Low Fire Adjuster (Governor Type) (Under dust cap)
MCS 320, 400 & 535 Valve Adjustment
Legend
2. High Fire Adjuster (Gate Type) (Make small adjustments only)
3. Low Fire Adjuster (Governor Type) (Under dust cap)
A flue gas analyser must be used to ensure that the correct combustion setting is achieved.
This is undertaken by inserting the analysers probe in to plugged hole within the flue collector of the
appliance or in the tapping in the flue immediately above the appliance if present.
The combustion setting required for all ProCon appliances are as detailed in the following table.
Boiler Type
Module
Range
Fuel
O2% at pmax
CO
2
% at
Max Output
O2% at pmin
CO
2
% at Min
Output
MCS 210
10-100kW
Nat Gas G20
4.8
9.10
5.2
8.90
MCS 210
10-100kW
Propane G31
5.5
8.70
5.8
8.55
MCS 260
25-125kW
Nat Gas G20
4.8
9.10
5.2
8.90
MCS 260
25-125kW
Propane G31
5.5
8.70
5.8
8.55
MCS 320
30-150kW
Nat Gas G20
4.8
9.10
5.2
8.90
MCS 320
30-150kW
Propane G31
5.5
8.70
5.8
8.55
MCS 400
38-190kW
Nat Gas G20
4.8
9.10
5.2
8.90
MCS 400
38-190kW
Propane G31
5.5
8.70
5.8
8.55
MCS 535
50-249.5kW
Nat Gas G20
4.8
9.10
5.2
8.90
MCS 535
50-249.5kW
Propane G31
5.5
8.70
5.8
8.55