Delta MCS-1800 Service Manual Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 70
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
© MHG Heating Ltd
52
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR
Telephone 08456 448802 Fax 08456 448803 Email info@mhgheating.co.uk Web www.mhgheating.co.uk
020315 Draft
Programing a Replacement GFA Module Controller
Replacement GFA Module controller are supplied for use in any location within the cascade.
The GFA module control will require programming prior to re-commissioning the combustion.
A cascade communication error message will be displayed if the following process is not undertaken.
**Prior to undertaking any work with a PCB please earth yourself by touching a secure earth connection
within the boiler.**
1. Check the build version of the Theta Controller. Data Badge on Rear of unit. This must be >E05.
2. Check the software version of the Theta Controller by switching the unit ON and pressing and
holding the “I” Button. The version must be 20:03 V 3.3 or greater.
3. Electrically isolate the Theta Controller and all or the modules.
Disconnect the module electrical connections. Dedicated plugs are used to prevent
misapplication.
1, Locking Tab connectors. 2, BUS 1 Connectors, 3 GFA Controller Housing
Page view 51
1 2 ... 47 48 49 50 51 52 53 54 55 56 57 ... 69 70

Comments to this Manuals

No comments