DELTA MCS-1800 3U Power Shelf
Installation, Operations and
Maintenance Manual
4-6
Settings Description Comment
Function
Battery Max. Capacity
Default
Range
Parameter
Default
Range
- 74AH
- 1~2500 AH
- 4
- 1~20
Temperature Shut Down
Function
Default
Recovery
- High Temperature Shutdown
- 149
- 122
Control:
Settings Description Comment
Remote SMR On/Off
- Function
- Remote SMR on/off capability exists through the
CSU control.
- Description - CSU automatically shuts down SMR in case of
DC high voltage.
- Users can manually shut down SMR from
Remote Management System.
SMR Shutdown
(1-3)
Floating / Equalize control
- Function
- SMR floating/equalize status can be set through
the CSU control.
- Description
- CSU automatically transfer SMR to floating
mode in case of mains recover after deep
discharge resulted from blackout/battery test
- Users can manually set SMR to floating or
equalize from CSU.
HVSD Recovery
- Function
- When system HVSD alarm recovery and system
voltage reduce to normal, this function is used to
reset the HVSD alarm