Delta MCS-1800 Specifications Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
NEW!
931
POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
ORDERING INFORMATION
ADVANCED KWH/DEMAND METER
H-SERIES CLASS 500 SUBMETERS
MAINS LINE VOLTAGE AND CURRENT SENSOR WIRING DIAGRAMS (CURRENT SENSORS INCLUDED)
H50-
07KIT
H Series Class 500 Submeter
208
480
600
100
200
400
800
1600
3200
208V meter
480V meter
600V meter
100A input
200A input
400A input
800A input
1600A input
3200A input
Indoor use only
J
MODEL DESCRIPTION
Outdoor use (NEMA 4x)R
H50- 480 100 J
03KIT
Example: 480V, 100A meter, BACnet MS/TP
and Ethernet
H50- 480 100 J
N
Example: 480V, 100A Green Net meter, BACnet
MS/TP and Ethernet EZ-7
03KIT
-or-
Lonworks and Ethernet EZ-7
03KIT
05KIT
06KIT
BACnet MS/TP and Ethernet
BACnet IP and RS-485 EZ-7
Modbus RCP/IP and Modbus RTU
Modbus RTU and Ethernet EZ-702KIT
07KIT
N
Green Net Option
62-0304—05 6
3-phase, 4-wire installation diagram.
3-phase, 3-wire installation diagram.
B W
N
LINE VOLTAGE
ØA
ØC
ECRUOSDAOL
ØB
B W
M32788
ØA
ØA ØB ØC
ØB
B W
CURRENT SENSORS
ØC
N
NOTES: LINE VOLTAGE CONNECTIONS: 14-22 AWG
SENSOR CONNECTIONS: B=BLACK LEAD, W=WHITE LEAD
1/10A, 600 VAC INLINE FUSE PER CONDUCTOR.
LITTLEFUSE PART NUMBER KLDR 100.
NEUTRAL NOT USED IN DELTA SYSTEM. REMOVE NEUTRAL
TERMINAL BLOCK SCREW FOR DELTA SYSTEMS.
B W
N
LINE VOLTAGE
Ø
A
ØC
ECRUOSDAOL
ØB
B W
M32797
ØA
ØA ØB ØC
ØB
B W
CURRENT SENSORS
ØC
NOTES: LINE VOLTAGE CONNECTIONS: 14-22 AWG
SENSOR CONNECTIONS: B=BLACK LEAD, W=WHITE LEAD
1/10A, 600 VAC INLINE FUSE PER CONDUCTOR.
LITTLEFUSE PART NUMBER KLDR 100.
NEUTRAL NOT USED IN DELTA SYSTEM. REMOVE NEUTRAL
TERMINAL BLOCK SCREW FOR DELTA SYSTEMS.
March 2014
Page view 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 65 66

Comments to this Manuals

No comments