POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
Secondary 0-5A
Frequency 50-400 Hz
Terminations Brass stud terminal with nut, flat
washer, lockwasher
Materials Of Construction
Plastic, UL94V-1
Insulation Class 600V, 10 kV BIL
Continuous Thermal Current
Resistor Factor 1.33 @ 30°C ambient (86°F) 1.0 @
55°C ambient (131°F)
Window Size 4.1" x 7.1" (10.4 x 18.0 cm),
4.1" x 11.7" (10.4 x 29.7 cm)
Weight 8 lb (3.6 kg)
Approvals UL-recognized component,
File #E238872; CSA certified,
File #245941
Warranty 1 year
SPLIT-CORE CURRENT TRANSFORMERS
500T, 501T
0.75 (1.91)
Four
Mounting
Holes
0.31" (0.79)
dia
LABEL
0.44
(1.12)
B3
1.63
(4.14)
B2
B1
A3
A2
THIS END REMOVABLE
A1
H1
X1
500T
4.1 (10.4)
6.4 (16.3)
7.3 (18.5)
7.1 (18.0)
10.0 (25.4)
10.9 (27.7)
501T
4.1 (10.4)
6.4 (16.3)
7.3 (18.5)
11.7 (29.7)
14.5 (36.8)
15.4 (39.1)
A1
A2
A3
B1
B2
B3
DIMENSIONS
MODEL
in
(cm)
DESCRIPTION
Model 500T and 501T Split-Core Current Transformers
provide a low-amperage current output proportional to line
current and are for use in energy management control and
metering applications. These transformers are ideal for
use as inputs to power monitors such as the EnGenius™
and current transducers such as Models 4CTV and 4CMA.
These transformers are designed to be assembled around an
existing insulated conductor without the need for dismantling
the primary bus or cables. The portion of the transformers
marked "This End Removable" can be disassembled and
then reassembled around the conductors that require current
monitoring.
FEATURES
5A secondary
Split-core construction for easy installation
Brass stud terminals #8-32 with one flat washer,
lockwasher, and regular nut
DIMENSIONS
SPECIFICATIONS
ORDERING INFORMATION
ACCURACY CLASS
WITH UNITY
POWER FACTOR
MODEL 500T - 4.1" x 7.1" (10.4 x 18.0 cm) Window
CURRENT
RATIO
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
4000:5
B0.1
2.5 VA
4.8
4.8
2.4
2.4
1.2
1.2
1.2
0.6
0.6
0.6
0.3
B0.2
5 VA
4.8
2.4
1.2
1.2
1.2
0.6
0.6
0.6
B0.5
12.5 VA
2.4
2.4
2.4
1.2
1.2
0.6
ANSI METER CLASS @ 60Hz ACCURACY CLASS
WITH UNITY
POWER FACTOR
MODEL 501T - 4.1" x 11.7" (10.4 x 29.7 cm) Window
MODEL
501T-102
501T-122
501T-152
501T-202
501T-252
501T-302
501T-352
501T-402
CURRENT
RATIO
1000:5
1200:5
1500:5
2000:5
2500:5
3000:5
3500:5
4000:5
B0.1
2.5 VA
2.4
1.2
1.2
0.6
0.6
0.6
0.6
0.3
B0.2
5 VA
4.8
2.4
1.2
1.2
0.6
0.6
0.6
0.6
B0.5
12.5 VA
2.4
2.4
1.2
1.2
0.6
0.6
ANSI METER CLASS @ 60Hz
Example: 500T-102 Split-core current transformer
with a current ratio of 1000:5 and a window
size of 4.1" x 7.1" (10.4 x 18.0 cm)
MODEL
500T-301
500T-401
500T-501
500T-601
500T-751
500T-801
500T-102
500T-122
500T-152
500T-162
500T-202
500T-252
500T-302
500T-402
±1% @ 7.5 VA
±1% @ 10.0 VA
±1% @ 12.5 VA
±1% @ 15.0 VA
±1% @ 25.0 VA
±1% @ 25.0 VA
±1% @ 25.0 VA
±1% @ 25.0 VA
±5% @ 1.5 VA
±3% @ 2.5 VA
±2% @ 2.5 VA
±1% @ 4.0 VA
±1% @ 5.0 VA
±1% @ 5.0 VA
±1% @ 7.5 VA
±1% @ 10.0 VA
±1% @ 12.5 VA
±1% @ 12.5 VA
±1% @ 15.0 VA
±1% @ 25.0 VA
±1% @ 25.0 VA
±1% @ 25.0 VA
500T
(shown with end removed)
CAUTION: Proper safety precautions must be followed
by a trained electrician during installation. It is
recommended that the incoming power be de-energized
before installation. The current transformer must have
its secondary terminals short-circuited or the burden
(load) connected before energizing the primary circuit.
For indoor use only. Use on insulated conductors only.
March 2014