POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
Secondary 0-5A
Frequency 50-400 Hz
Insulation Class 600V, 10 kV BIL, Full Wave
Lead Wires 24" (61 cm), 16 AWG
Materials Of Construction
Plastic, UL94V-1
Weight
2RL 0.5 lb (0.23 kg)
5RL 1.0 lb (0.45 kg)
7RL 1.5 lb (0.63 kg)
8RL 2.5 lb (1.2 kg)
Approvals UL-recognized component,
File #E238872; CSA File #245941
Warranty 1 year
SOLID-CORE CURRENT TRANSFORMERS
RL SERIES
DESCRIPTION
The RL Series Solid-Core Current Transformers provide a
low-amperage current output proportional to line current and
are for use in building automation and metering applications.
These low-cost current transformers are ideal as inputs
to power monitors, such as the EnGenius and current
transducers, such as Models 4CTV and 4CMA.
FEATURES
5A secondary
Flexible leads are UL 1015 105°C, CSA approved, #16
AWG, 24"L (61 cm)
UL recognized component, CSA certified
SPECIFICATIONS
ORDERING INFORMATION
CURRENT
RATIO
MODELS
CURRENT
RATIO
CODE
MODEL
2RL
Outer
dia 2.46" (6.25 cm)
Window
dia 1.05" (2.67 cm)
MODEL
5RL
Outer
dia 3.56'' (9.0 cm)
Window
dia 1.56'' (3.9 cm)
MODEL
7RL
Outer
dia 4.58" (11.6 cm)
Window
dia 2.50" (6.4 cm)
MODEL
8RL
Outer
dia 5.73'' (14.6 cm)
Window
dia 3.25'' (8.3 cm)
Accuracy
%
50:5
75:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
750:5
800:5
1000:5
1200:5
1600:5
2000:5
2500:5
500
750
101
151
201
251
301
401
501
601
751
801
102
122
162
202
252
±3
±2
±1
±1
±1
±1
±1
±1
--
--
--
--
--
--
--
--
--
2.0
2.0
2.0
4.0
4.0
6.0
8.0
10.0
--
--
--
--
--
--
--
--
--
1.0
1.5
2.0
5.0
5.0
10.0
12.5
12.5
20.0
25.0
25.0
25.0
25.0
--
--
--
--
--
--
±2
±1
±1
±1
±1
±1
±1
±1
±1
±1
±1
±1
±1
--
--
Example:
Model
Current
Ratio
Code
Important! Shaded items in Ordering Information are available by special order and are not returnable for credit.
5RL 201
5RL201 Model RL current transformer with
1.56" (3.9 cm) window diameter and a 200:5
current ratio
VA
Accuracy
%
VA
Accuracy %
VA
Accuracy %
VA
±2
±2
±2
±1
±1
±1
±1
±1
±1
±1
±1
±1
±1
--
--
--
--
--
--
--
--
±1
±1
--
±1
±1
±1
--
±1
±1
--
--
±1
±1
--
--
--
--
5.0
7.5
--
25.0
35.0
50.0
--
60.0
75.0
--
--
120.0
50.0
--
--
2.5
5.0
5.0
5.0
12.5
15.0
25.0
30.0
30.0
35.0
35.0
35.0
45.0
--
--
CAUTION: Proper safety precautions must be followed
by a trained electrician during installation. It is
recommended that the incoming power be de-energized
before installation. The current transformer must have its
secondary terminals short-circuited or the burden (load)
connected before energizing the primary circuit. For
indoor use only. Use on insulated conductors only.
RL