Internal Current Sensing (for single-phase loads)
Models with internal current-sensing are great for direct-control and current-sensing of
exhaust fans, pumps, and other single-phase electrical loads up to 20A. The control relay
contacts of these models wire directly in series with single-phase motors using the wires
that exit the housing through the 1/2" conduit hub. The current of the load is sensed within
the housing. Low-voltage wiring from the controller for the control relay coil and status
switch enter the separate Class 2 wiring compartment in the housing through star bushings
or conduit and are connected to screw terminals.
Remote Current Sensing (for loads with motor starters)
Models with remote current-sensing are great for control and status sensing of electrical
loads that require a motor starter. The control relay contacts of these models are wired
in series with the motor starter coil using the two wires that exit the housing through the
1/2'' conduit hub. Currents up to 150A are sensed externally with a current sensing ring
connected to the two gray wires that also exit through the 1/2'' conduit hub. Low-voltage
wiring from the controller for the control relay coil and status switch enter the separate Class
2 wiring compartment in the housing through star bushings or conduit and are connected to
screw terminals.
APPLICATION
BAS Controller
Status In
Control Out
Current is sensed internally.
RIBX
Optional Override Switch
Closed/Open/Auto
Single Phase
Exhaust Fan
120-277 VAC
10 or 20A
Class 2
Current Sensor
and Control Relay
with Override Switch
On/Off
Internal Current Sensing
BAS Controller
Status In
Control Out
RIBX
Optional Override Switch
Closed/Open/Auto
Three-Phase
Power
Class 2
On/Off
Contactor
Motor
Starter
Relay Switches Motor
Starter Coil
Current Sensor
and Control Relay
with Override Switch
Toroid has no open
circuit voltage eliminating
electrical shock hazard.
Three-Phase
Motor
Remote Current Sensing
FUNCTIONAL DEVICES CURRENT SWITCH AND RELAY
RIBX SERIES
ORDERING INFORMATION
MODEL
CURRENT
SENSING
CURRENT SENSING
RANGE/THRESHOLD
OVER
SW
RELAY CONTACT
WIRING
RELAY CONTACT
RATINGS *
RELAY COIL AND
CURRENT SWITCH
RIBXLCA
RIBXLCEA
RIBXLCF
RIBXLCJA
RIBXLCJF
RIBXLCRA
RIBXLCRF
RIBXLSA
RIBXLSEA
RIBXLSF
RIBXLSJA
RIBXLSJF
RIBXLSRA
RIBXLSRF
RIBX24SBA
RIBX24SBF
Internal
Internal
Ye s
Ye s
0.5-10A/Adjustable
0.125-5A/Adustable
0.5-10A/Fixed, 0.5A
3-150A/Adjustable
3-150A/Fixed, 3A
1.25-150A/Adjustable
1.25-150A/Fixed, 1.25A
Split-core
Solid-core
0.5-20A/Adjustable
Internal
0.5-10A/Adjustable
0.125-5A/Adustable
0.5-10A/Fixed, 0.5A
10A resistive 120/240/277 VAC - 28 VDC
480 VA pilot duty 240/277 VAC
480 VA ballast 277 VAC
600W tungsten 120 VAC N.O
240W tungsten 120 VAC N.C.
1/3 hp for N.O. 120/240 VAC
1/6 hp for N.C. 120/240 VAC
1/4 hp for N.O. 277 VAC
1/8 hp for N.C. 277 VAC
10A resistive 277 VAC
480 VA pilot duty 277 VAC
480 VA ballast 277 VAC
600W tungsten 120 VAC N.O
240W tungsten 120 VAC N.C.
1/3 hp for N.O. 120/240 VAC
1/6 hp for N.C. 120/240 VAC
1/4 hp for N.O. 277 VAC
1/8 hp for N.C. 277 VAC
20A resistive 277 VAC
1110 VA pilot duty 277 VAC
770 VA pilot duty 120 VAC
20A ballast 277 VAC N.O.
10A ballast 277 VAC N.C.
10A tungsten 120 VAC N.O.
240W tungsten 120 VAC N.C.
2 hp 277 VAC
1 hp 120 VAC
1-SPDT
Relay
1-SPDT Relay
1-SPST Relay
1-SPST Relay
(blue)
(yellow)
(orange)
N.C.
COM
N.O.
(blue)
(yellow)
(orange)
N.C.
COM
N.O.
33 mA @ 10 VAC 13 mA @ 10 VDC
35 mA @ 12 VAC 15 mA @ 12 VDC
46 mA @ 24 VAC 18 mA @ 24 VDC
55 mA @ 30 VAC 20 mA @ 30 VDC
50 mA @ 18 VAC 33 mA @ 22 VDC
83 mA @ 24 VAC 35 mA @ 24 VDC
47 mA @ 30 VDC
Current
Sensor Status
10-30 VAC/VDC
Common
(orange)
(orange)
Closed
Open
Auto
(orange)
(orange)
Closed
Open
Auto
1
1
Relay
input current
Relay
input current
Relay coil wiring
Relay coil wiring
}
}
Current
Sensor Status
}
24 VAC/VDC
Common
}
Split-core
Solid-core
3-150A/Adjustable
3-150A/Fixed, 3A
1.25-150A/Adjustable
1.25-150A/Fixed, 1.25A
Internal
RIBX24BF
RIBXF
RIBXA
RIBXRF
RIBXRA
RIBXJF
RIBXJA
Internal
Internal
Solid-core
Solid-core
Split-core
Split-core
0.5-30A/Fixed, 0.5A
0.5-30A/Adjustable
1.25-150A/Fixed, 1.25A
1.25-150A/Adjustable
3-150A/Fixed, 3A
3-150A/Adjustable
Current switch only
Current switch only
Current switch only
Current switch only
Current switch only
Current switch only
RIBX24BA
0.5-20A/Fixed, 0.5A
0.5-20A/Adjustable
0.5-20A/Fixed, 0.5A
Current Sensor Wiring
Internal Models
(purple)
(purple)
Current
Sensor
(gray)
(gray)
Current
Sensor
Solid- and split-core models
(gray)
(gray)
Current
Sensor
Solid- and split-core models
Current switch wiring
Current
Sensor Status
}
Current switch output
Current switch wiring
RIBX243PA
RIBX243PF
0.5-20A/Adjustable
0.5-20A/Fixed, 0.5A
Internal
20A resistive @ 300 VAC, 28 VDC
20A ballast @ 277-480 VAC
15A resistive @ 600 VAC
770 VA pilot duty @ 120 VAC, 1 Ph
1158 VA pilot duty @ 240 VAC, 1 Ph
1110 VA pilot duty @ 277 VAC, 1 Ph
1640 VA pilot duty @ 480 VAC, 1 Ph
1466 VA pilot duty @ 240 VAC, 1 Ph
2112 VA pilot duty @ 480 VAC, 1Ph
Heavy Pilot Duty @ 600 VAC
7.5 HP @ 480 VAC, 3 Ph
5 HP @ 240 VAC, 3 Ph
3 HP @ 480-600 VAC, 1 Ph
2 HP @ 240-277 VAC, 1 Ph
1 HP @ 120 VAC, 1 Ph
(blue)
(blue)
N.O.
(yellow)
(yellow)
N.O.
(orange)
(orange)
N.O.
2
210 mA @ 24 VAC 154 mA @ 30 VDC
Relay input current
Current switch output
24 VAC/VDC
Common
}
Relay coil wiring
}
Current
Sensor Status
Note: 1 Internal yellow jumper determines if SPST contacts are N.O. or N.C. 2 Can be ordered N.C. by adding -NC after model number.