Delta MCS-1800 Specifications Page 42

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 41
NEW!
POWER MONITORING & PROTECTION
952
NEW!
POWER MONITORING & PROTECTION
16
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
CURRENT TRANSDUCERS
A/CT, A/SCT SERIES
Supply Voltage
A/CTA, A/SCTA 12 to 30 VDC
A/CTE, A/CTV,
A/SCTE, A/SCTV Induced from monitored conductor
Supply Current
A/CTA, A/SCTA 36 mA maximum
Frequency
A/CTA, A/SCTA 30 to 60 Hz
A/CTE, A/CTV,
A/SCTE, A/SCTV 50 to 600 Hz
Output
A/CTA, A/SCTA 4-20 mA, 2-wire, loop-powered
A/CTE, A/SCTE 0-5 VDC
A/CTV, A/SCTV 0-10 VDC
Output Impedance
A/SCTA 700 @ 24 VDC
A/SCTA-VFD 700 @ 24 VDC
Maximum Sensing Current Voltage
600 VAC
Isolation Rating 2200 VAC
Accuracy
A/CTA, A/SCTA ±0.5%
A/CTE, A/CTV,
A/SCTE, A/SCTV ±1%
Operating Temperature 5° to 104°F (-15° to 40°C)
VFD models 32° to 104°F (0° to 40°C)
Operating Humidity 0 to 95% (non-condensing)
Mounting DIN rail size 35 mm
Window Size 0.75", accepts up to 350 MCM cables
Weight 0.24 lbs (0.109 kg)
Approvals UL listed, File #E309723, CE
Warranty 5 years, limited
RoHS Statement Ye s
Enclosure Rating UL94-5VB
DESCRIPTION
Current sensors monitor the current flowing to electrical equipment.
The magnitude of the analog output signal is proportional to the
current flow through the wire. The A/CT series offers solid-core
sensors with 4-20mA, 0-5VDC, or 0-10VDC outputs. The A/SCT
series offers split-core sensors for retrofit applications with the same
available outputs. Sensors are available with various input current
ranges from 5 to 250 amps. True RMS models make monitoring of
VFD applications a snap.
FEATURES
Available in solid-core or split-core
5 VDC, 10 VDC or 4-20mA outputs
Voltage output models are self-
powered
Integral DIN rail mount
True RMS versions for VFD
applications
SPECIFICATIONS
A/CT
A/SCT
ORDERING INFORMATION
DIMENSIONS
MODEL DESCRIPTION
A/CTA-5 Solid-core, loop-powered current sensor, 0-5A input, 4-20 mA output
A/CTA-50 Solid-core, loop-powered current sensor, 0-10/20/50A input, 4-20 mA output
A/CTA-250 Solid-core, loop-powered current sensor, 0-100/200/250A input, 4-20 mA output
A/CTA-50-VFD Solid-core, loop-powered true RMS current sensor, 0-10/20/50A input, 4-20 mA output
A/CTA-250-VFD Solid-core, loop-powered true RMS current sensor, 0-100/200/250A input, 4-20 mA output
A/SCTA-5 Split-core, loop-powered current sensor, 0-5A input, 4-20 mA output
A/SCTA-50 Split-core, loop-powered current sensor, 0-10/20/50A input, 4-20 mA output
A/SCTA-200 Split-core, loop-powered current sensor, 0-100/150/200A input, 4-20 mA output
A/SCTA-50-VFD Split-core, loop-powered true RMS current sensor, 0-10/20/50A input, 4-20 mA output
A/SCTA-200-VFD Split-core, loop-powered true RMS current sensor, 0-100/150/200A input, 4-20 mA output
A/CTE-50 Solid-core, self-powered current sensor, 0-10/20/50A input, 0-5 VDC output
A/CTE-250 Solid-core, self-powered current sensor, 0-100/200/250A input, 0-5 VDC output
A/CTV-50 Solid-core, self-powered current sensor, 0-10/20/50A input, 0-10 VDC output
A/CTV-250 Solid-core, self-powered current sensor, 0-100/200/250A input, 0-10 VDC output
A/SCTE-50 Split-core, self-powered current sensor, 0-10/20/50A input, 0-5 VDC output
A/SCTE-250 Split-core, self-powered current sensor, 0-100/200/250A input, 0-5 VDC output
A/SCTV-50 Split-core, self-powered current sensor, 0-10/20/50A input, 0-10 VDC output
A/SCTV-250 Split-core, self-powered current sensor, 0-100/200/250A input, 0-10 VDC output
2.84
(7.2)
0.50 (1.3)
Ø0.22
(0.6)
Typ.
Top View
0.76
(1.9)
0.74
(1.9)
3.33 (3.8)
1.38 (3.5)
0.14
(0.4)
in
(cm)
3.38 (8.6)
1.38 (3.5)
0.14
(0.4)
Ø0.78
(2.0)
2.84
(7.2)
0.40 (1.0)
Ø0.21
(0.5)
Typ.
Top View
A/SCTA, A/SCTE, A/SCTVA/CTA, A/CTE, A/CTV