NEW!
POWER MONITORING & PROTECTION
954
NEW!
POWER MONITORING & PROTECTION
16
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
APPLICATION
Internal Current Sensing
The RIBX-V Series with internal current sensing is great for direct control and analog current sensing of exhaust fans, pumps, and other
single-phase electrical loads up to 20A. The control relay contacts of these models wire directly in series with single-phase motors using
the wires that exit the housing through the 1/2" conduit hub. The current of the load is sensed within the housing. Low-voltage wiring from
the controller for the control relay coil and analog current signal enter the separate Class 2 wiring compartment in the housing through
star bushings or conduit and are connected to screw terminals.
BAS Contoller
Analog In
Control Out
Current is sensed internally.
RIBX-V
Optional Override Switch
Closed/Open/Auto
Single Phase
Exhaust Fan
120-277 VAC
5, 10, 20, or 30A
Class 2
0-5 or 0-10 VDC
Analog Current Sensor
and Control Relay
with Override Switch
On/Off
Internal Current Sensing
CURRENT TRANSDUCER AND RELAY
RIBX-V SERIES
ORDERING INFORMATION
MODEL CURRENT
SENSING
CURRENT SENSING
RANGE (amps)
OVER
SW
RELAY CONTACT
WIRING
RELAY CONTACT
RATINGS
RELAY COIL AND
ANALOG OUTPUT
RIBXLCEV
RIBXLSEV
RIBXLCV
RIBXLSV
RIBX24BV
RIBX24SBV
RIBXV
Internal
Internal
Ye s
Ye s
0-5
0-30
0-10
Internal
0-20
Internal
RIBX243PV 0-20 Internal
10A resistive 120/240/277 VAC - 28 VDC
480 VA pilot duty 240/277 VAC
480 VA ballast 277 VAC
600W tungsten 120 VAC N.O
240W tungsten 120 VAC N.C.
1/3 hp for N.O. 120/240 VAC
1/6 hp for N.C. 120/240 VAC
1/4 hp for N.O. 277 VAC
1/8 hp for N.C. 277 VAC
5A resistive 277 VAC
345 VA pilot duty 120/240 VAC N.O.
211 VA pilot duty 120/240 VAC N.C.
268 VA pilot duty 277 VAC N.O.
175 VA pilot duty 277 VAC N.C.
1/3 hp for N.O. 120/240 VAC
1/6 hp for N.C. 120/240 VAC
1/4 hp for N.O. 277 VAC
1/8 hp for N.C. 277 VAC
20A resistive 277 VAC
1110 VA pilot duty 277 VAC
240W tungsten N.C. 120 VAC
770 VA pilot duty 120 VAC
1 hp 120 VAC
2 hp 277 VAC
20A ballast N.O. 277 VAC
10A ballast N.C. 277 VAC
10A tungsten N.O. 120 VAC
Not rated for electrical.
20A resistive 300 VAC
20A resistive 28 VDC
15A resistive 600 VAC
1 hp 120 VAC, 1 Ph
2 hp 240-277 VAC, 1 Ph
3 hp 480-600 VAC, 1 Ph
5 hp 240 VAC, 3 Ph
7.5 hp 480 VAC, 3 Ph
20A ballast 277-480 VAC
RIBXLCEV, RIBXLCV
1-SPDT Relay
1-SPDT Relay
RIBXLSEV, RIBXLSV
1-SPST Relay
1-SPST Relay
(blue)
(yellow)
(orange)
N.C.
COM
N.O.
(blue)
(yellow)
(orange)
N.C.
COM
N.O.
(blue)
(blue)
N.O.
(yellow)
(yellow)
N.O.
(orange)
(orange)
N.O.
30 mA @ 10 VAC 12 mA @ 10 VDC
32 mA @ 12 VAC 14 mA @ 12 VDC
42 mA @ 24 VAC 16 mA @ 24 VDC
50 mA @ 30 VAC 18 mA @ 30 VDC
75 mA @ 24 VAC, 32 mA @ 24 VDC
(orange)*
(orange)*
Closed
Open
Auto
(orange)
(orange)
Closed
Open
Auto
Internal yellow jumper determines if SPST contacts are N.O. or N.C.
* Not rated for electrical ballast.
Order N.C. by adding -NC after model number.
1
1
2
Relay input current
Relay input current
0-10 VDC
0-5 VDC
Common
Analog out wiring
}
Analog out wiring
10-30 VAC/VDC
Common
}
24 VAC/VDC
Common
}
Current transducer only, 0-30A
Note:
Ye s
*Gray wire on RIBXLSEV
Current Sensor
Wiring
(purple)
(purple)
Current
Sensor
Relay coil wiring
Relay coil wiring
}
0-10 VDC
0-5 VDC
Common
190 mA @ 24 VAC
Relay input current
Analog out wiring
24 VAC/VDC
Common
}
Relay coil wiring
}
0-10 VDC
Common
}
0-10 VDC
0-5 VDC
Common
Analog out wiring
21
*
*
*
*