POWER MONITORING & PROTECTION
POWER MONITORING & PROTECTION
16
WE MAKE IT EASY.
kele.com 888-397-5353 USA
Supply Voltage 24 - 40 VDC
Frequency 50 - 60 Hz
V Models 10 - 400 Hz
Output 4 - 20 mA, loop-powered
Output Impedance 600 max @ 24 VDC
Insulation Voltage 600 VAC
Accuracy 1.0% FS
Response Time 500 ms to 90% of step change
Overrange Limit Sensor self-limits to 25 mA output
Terminations Screw terminals
Materials Of Construction
UL 94 flammability rated
thermoplastic
Weight 1.3 lb (0.6 kg)
Approvals UL and ULC listed, File #E129625,
CE pending
Warranty 5 years
ORDERING INFORMATION
HIGH AC CURRENT TRANSDUCERS WITH CURRENT OUTPUT
SENTRY 200-A SERIES
Aperture
3
(7.63)
4.22
(10.7)
4.5
(11.43)
in
(cm)
1.9
(4.83)
Depth
DESCRIPTION
The Sentry 200-A Series High AC Current Transducers with
Current Output can be used to directly monitor up to 2000A
without requiring an additional current transformer. The output
from these transducers is a 4-20 mA signal.
FEATURES
Eliminates the need for a current transformer
Large aperture to accommodate large conductors or
wire bundles
Loop powered 4-20 mA output
Multi-range input eliminates zero and span
adjustments
Easy installation with integral mounting brackets
+
4-20 mA
Load
Power
Supply
24 VDC
Typical
+
+ -
Sentry
200-A
Monitored Conductor
WIRING
DIMENSIONS
SPECIFICATIONS
200-3-A
MODEL DESCRIPTION
200-3-A Solid-core high current transducer, 0-750A, 4-20 mA output
200-3-A-V Solid-core high current transducer, 0-750A, 4-20 mA output (10 - 400 Hz)
200-4-A Solid-core high current transducer, 0-2000A, 4-20 mA output
200-4-A-V Solid-core high current transducer, 0-2000A, 4-20 mA output (10 -400 Hz)
MODEL RANGE SWITCH MAX CONT MAX FOR MAX FOR
POSITION 6 SEC 1 SEC
(amps)
200-3-A 0-375 375 750 1500 3750
0-500 500
0-750 750
200-4-A 0-1000 1000 2000 4000 10,000
0-1333 1333
0-2000 2000
Output 4-20 mA, loop-powered
Supply voltage 24-40 VDC
Output load 600 max @ 24 VDC
Rmax = (V supply-12)/0.020
Accuracy 1.0% FS
Frequency 50-60 Hz, (V models 10-400 Hz)
Response time 500 ms to 90% of step change
Case UL 94 flammability rated thermoplastic
Weight 1.3 lb (0.6 kg)
Agency approvals UL and ULC listed, File # E129625,
CE certified
Insulation class 600 VAC
Overrange limit Sensor self-limits to 25 mA output
Termination Screw terminals
Warranty 5 years
Note: The standard models are average responding. Also
available are variable frequency integration models
for monitoring the load side of a VFD.
Note: The standard models are average responding. Also
available are variable frequency integration models for
monitoring the load side of a VFD.