Delta MCS-1800 Specifications Page 46

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 45
NEW!
POWER MONITORING & PROTECTION
956
NEW!
POWER MONITORING & PROTECTION
16
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
B258B 258B A258B A269 B269 C269
Nominal AC Voltage (VAC phase to phase) 120 208/240 480 120 208/240 480
Adjustment Range (VAC) 85-120 160-240 380-480 110-145 210-280 400-540
80-115 170-240 380-460
Frequency (Hz) 60 60 60 60 60 60
Power Consumption (W) 0.75 1.5 4.5 1.5 3.0 6.0
Response Time 50ms 50ms 50ms Adj. 1-10 sec Adj. 1-10 sec Adj. 1-10 sec
Reset Time 50ms 50ms 50ms 0.25 sec 0.25 sec 0.25 sec
Mounting RB08-PC RB08-PC RB08-PC Surface Surface Surface
Weight oz (g) 5 (141.7) 5 (141.7) 5 (141.7) 9 (255.1) 9 (255.1) 9 (255.1)
Agency Approvals (UL file #E60400) UR, CSA UR, CSA UR*, CSA UL, CSA UL, CSA UL, CSA
Repeat Accuracy ±0.1% of setpoint (fixed conditions)
Reset Type Automatic
Deadband Approx 2%
Output Contacts SPDT
Contact Rating 10A @ 240 VAC, resistive
* Condition of acceptability: A258B must be used with the
RB08-PC socket.
Operating temp -20° to 131°F (-30° to 55°C)
Humidity 0-97% noncondensing
Dimensions
258 1.95"H x 1.95"W x 3.25"D
(4.96 x 4.96 x 8.25 cm)
RB08-PC 2.25"H x 2.0"W x 0.625"D
(5.7 x 5.1 x 1.6 cm)
269 6.06"H x 3.88"W x 2.82"D
(15.4 x 9.9 x 7.1 cm)
Warranty 5 years
ORDERING INFORMATION
THREE-PHASE VOLTAGE MONITORS
258, 269
DESCRIPTION
Models 258 and 269 continuously monitor three-phase
power lines for phase loss, phase reversal, and low voltage.
Model 269 also monitors for high voltage. Models 258 and
269 do not require a neutral connection and can be used
with any Wye or Delta systems. When correct voltage and
phase rotation are applied, the internal relay will energize.
A fault condition will de-energize the relay. When the fault is
corrected, the monitor will automatically reset.
L3
L2
L1
Control
Voltage
Optional Alarm Indicator
M
M
M
M
Start
Stop
Model 269
Motor
C
B
A
M
M
M
1
2
8
543
L3
Control
Voltage
Motor
Stop
Model
258
Start
L2
L1
M
M
M
Shown de-energized
258
Shown de-energized
269
WIRING
MODEL DESCRIPTION
A258B Three-phase voltage monitor, 480 VAC
258B Three-phase voltage monitor, 208/240 VAC
B258B Three-phase voltage monitor, 120 VAC (use with Model 3PT3 potential transformer)
RB08-PC 600V/10A socket (required with each 258 voltage monitor)
A269 Three-phase voltage monitor, 120 VAC (use with Model 3PT3 potential transformer)
B269 Three-phase voltage monitor, 208/240 VAC
C269 Three-phase voltage monitor, 480 VAC
SPECIFICATIONS
258
269
March 2014
Page view 45